Figure 7-11 Figure 7-12
SIDEWALL VENTING WITH
CONCENTRIC VENT KIT
AND VERTICAL PIPING
ALL HORIZONTAL
EXTERIOR WALL
VENT
EXHAUST
RIGHT SIDE VIEW
MUST BE FACING UP
NOTE: INTAKE LEG
SUPPORT BRACKETS
MUST BE USED ON
INTAKE AIR
VENT
1" MIN.
AND VERTICAL PIPINGFRONT VIEWEXTERIOR WALLMUST BE FACING UPALL HORIZONTAL NOTE: INTAKE LEGEXHAUSTVENTSUPPORT BRACKETSMUST BE USED ONINTAKE AIRVENT1" MIN.

SIDEWALL VENTING WITH

CONCENTRIC VENT KIT

GENERAL NOTE: All vent pipes must be glued, properly supported and the exhaust must be pitched a
minimum of a ΒΌ" per foot back to the heater (to allow drainage of condensate).
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the
appliance and the balance at 4 foot invervals on the vent pipe. The boiler venting must be readily
accessible for visual inspection for the first three feet from the boiler.