Munchkin Gas-Fired Hot Water Circulating Heater Installing Exhaust Vent and Intake AIR Vent

Models: Gas-Fired Hot Water Circulating Heater

1 72
Download 72 pages 25.19 Kb
Page 37
Image 37

GAS-FIRED HEATER Installation Manual

PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

DANGER

Munchkin Contender Heater must be vented as detailed in Venting section Part 7. Ensure the exhaust and intake piping comply with these instructions regarding vent system.

Inspect finished combustion air intake and exhaust piping thoroughly to ensure all joints are well secured and airtight and comply with all applicable code requirements, as well as with the instructions provided in this manual.

Failure to provide a properly installed vent system will cause severe personal injury or death.

A.INSTALLING EXHAUST VENT AND INTAKE AIR VENT

WARNING

This vent system will operate with a positive pressure in the pipe. Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure.

Follow the venting instructions below carefully. Failure to do so may result in severe personal injury, death, or substantial property damage.

a.Non Foam Core PVC (Polyvinyl Chloride) Pipe conforming to ASTM D-1785).

b.Non Foam Core CPVC (Chlorinated Polyvinyl Chloride) Pipe conforming to ASTM D-1785).

c.Non Foam Core ABS (Acrylonitrile- Butadiene- Styrene) Pipe conforming to ASTM D3965 Class 3-2-2-2-2.

WARNING

Do not use Foam Core Pipe in any portion of the exhaust piping from this heater. Use of Foam Core Pipe may result in severe personal injury, death, or substantial property damage.

2.Cellular foam core piping may be used on air inlet piping only. Never use cellular foam core material for exhaust vent piping.

D.EXHAUST VENT AND INTAKE AIR VENT PIPE LOCATION

WARNING

Both exhaust and intake air vents must exit from the same side of the building to assure correct appliance operation.

B.GENERAL

1.Install the Munchkin Contender venting system in accordance with these instructions and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, CAN/CGA B149, and/or applicable provisions of local building codes. Vent installations in Canada must comply with ULC S636. The Recommended manufacturer for this application is Ipex of Canada Model System 636.

2.This heater is a direct vent appliance and is listed as a Category IV appliance with Underwriters Laboratories, Inc. VENT AND INTAKE AIR PIPE

C.APPROVED MATERIALS FOR EXHAUST VENT AND INTAKE AIR VENT

1.Use only Non Foam Core venting material. The following materials are approved for use as vent pipe for this heater:

1.Determine exhaust vent location:

a.The vent piping for this heater is approved for zero clearance to combustible construction.

b.See illustration within this section of clearances for location of exit terminals of direct-vent venting systems.

c.This heater vent system shall terminate at least 3 feet (0.9 m) above any forced air intake located within 10 ft (3 m). Note: this does not apply to the combustion air intake of a direct-vent appliance.

d.Provide a minimum of 1 foot distance from any door, operable window, or gravity intake into any building.

e.Provide a minimum of 1 foot clearance from the bottom of the exhaust above the expected snow accumulation level. Snow removal may be necessary to maintain clearance.

36

Page 37
Image 37
Munchkin Gas-Fired Hot Water Circulating Heater installation manual Installing Exhaust Vent and Intake AIR Vent, General