GAS-FIRED HEATER Installation Manual
PART 11. START-UP PREPARATION
A. CHECK/CONTROL WATER CHEMISTRY | ically due to degradation of inhibitors over time. |
| Follow all fluid manufacturer’s instructions. |
WARNING
Do not use
Water pH between 6.0 and 8.0
1.Maintain heater water pH between 6.0 and 8.0. Check with litmus paper or have chemically analyzed by water treatment company.
2.If pH differs from above, consult local water treatment company for treatment needed.
Hardness less than 7 grains.
1.Consult local water treatment companies for unusually hard water areas (above 7 grains hardness).
Chlorine concentration less than 200 ppm
1.Filling with chlorinated fresh water should be acceptable since drinking water chlorine levels are typically less than 5 ppm.
2.Do not use the heater to directly heat swimming pool or spa water.
3.Do not fill heater or operate with water containing chlorine in excess of 200 ppm.
Clean system to remove sediment
1.You must thoroughly flush the system (without heater connected) to remove sediment. The
2.For zoned systems, flush each zone sepa- rately through a purge valve. (If purge valves and isolation valves are not already installed, install them to properly clean the system.)
3.Flush system until water runs clean and you are sure piping is free of sediment.
Test/replace freeze protection fluid
1.For systems using freeze protection fluids, follow fluid manufacturer’s instructions to verify inhibitor level and that other fluid characteristics are satisfactory.
2.Freeze protection fluid must be replaced period-
B. FREEZE PROTECTION (WHEN USED)
WARNING
NEVER use automotive or standard glycol antifreeze, even ethylene glycol made for hydronic systems. Use only
Throroughly clean and flush any system that has has used glycol before installing the new Contender Contender Heater.
Provide Munchkin Contender Heater owner with a material safety data sheet (MSDS) on the fluid used.
1.Determine freeze protection fluid quantity using total system water content, following fluid manufacturer’s instructions. Remember to include expansion tank water content.
2.Local codes may require back flow preventer or actual disconnect from city water supply.
3.When using freeze protection fluid with automatic fill, install a water meter to monitor water makeup. Freeze protection fluid may leak before the water begins to leak, causing concentration to drop, reducing the freeze protection level.
C.FILL AND TEST WATER SYSTEM
1.Fill system only after ensuring the water meets the requirements of this manual.
2.Close manual and automatic air vents and heater drain valve.
3.Fill to correct system pressure. Correct pressure will vary with each application.
a.Typical cold water fill pressure for a residential system is 12 psi.
b.Pressure will rise when heater is turned on and system water temperature increases. Operating pressure must never exceed 25 psig.
4.At initial fill and during heater startup and testing, check system thoroughly for any leaks. Repair all leaks before proceeding further.
51