Murphy BCEG-12-10 Specifications, Power Supply, DC Charge Output, Charge Fail Output, General

Models: BCEG-12-10 BCEG-24-20 BCEG-24-10

1 20
Download 20 pages 52.34 Kb
Page 18
Image 18

Specifications

Power Supply

Nominal operating voltages – 120V Units

Permissible voltage variation - ± 6% of nominal

Nominal operating frequency – 50/60Hz

DC Charge Output

Maximum current ADC – 20

Nominal voltage VDC – 12 or 24

Float/boost voltages

These are factory preset for specified batteries, typical settings are as follows:

Vented lead acid – Float voltage – 12V / 13.6V and 24V / 27.2V

Vented lead acid – Boost voltage – 12V / 14.1V and 24V / 28.2V

Charge Fail Output

Relay type – volt free SPDT contacts relay de-energized on fault.

Contact rating – 1A @ 30VDC (resistive load)

General

Transformer – Single phase 50-60 Hz Class 155 (F)

Operating temperature - +14°F to +131°F (-10°C to +55°C)

Wall mounted enclosure models

BCEG-12-10, BCEG-24-10 – dimensions 10.9”/278mm(W) x 4.7”/120mm(L) x 11”/280mm(H); weight 22 pounds / 10.0Kg

BCEG-24-20 – dimensions 11.8”/300mm(W) x 11.8”/300mm(L) x 8.3”/210mm(H), weight 38.5 pounds / 17.5Kg

EMC emission/immunity – EN58801-2 / EN50082-2

Section 75

00-02-0615

02-29-08

- 14 -

Page 18
Image 18
Murphy BCEG-12-10, BCEG-24-20, BCEG-24-10 manual Specifications, Power Supply, DC Charge Output, Charge Fail Output, General