Current Limiting
The Guardian battery charger is current limited and will only output the rated current of the charger.
Guardian Current Ratings
Model Rating
Battery Charged Condition
When charged, the battery will only accept a charge to replace the losses within the battery (approximately 1mA per AH of battery). If there is a standing load (the panel controller, etc.) the charger will output the standing load plus the losses to the battery. If a standing load of 1A is present with 50AH Vented Lead Acid batteries then the charger will supply 1.05 amps.
A charged battery with open circuit terminals (no load connected) will always be higher than nominal battery voltage (12.6 on a 12V lead acid battery).
Dimensions
Model | W | D | H | Weight |
10.83” | 4.92” | 11” | 22 lbs. | |
| (275mm) | (125mm) | (280mm) | (10.0Kg) |
10.9” | 4.7” | 11” | 22 lbs. | |
| (278mm) | (120mm) | (280mm) | (10.0Kg) |
13.19” | 7.71” | 12.20” | 38.5 lbs. | |
| (335mm) | (145mm) | (310mm) | (17.5Kg) |
Section 75 | |