Murphy MDTM89 specifications One Thermocouple Only, Open Thermocouple Input, Mounting Dimensions

Models: MDTM89

1 4
Download 4 pages 28.06 Kb
Page 2
Image 2
MOUNTING DIMENSIONS

MOUNTING DIMENSIONS

Mount the MDTM89 temperature SWICHGAGE® in a place where it will be protected from rain and splashing water. A minimum distance of 12 in. (305 mm) from any ignition coils or coil leads should be main- tained. The MDTM89 flush mount case is intended for mounting in a flat panel .032 in. (1 mm) to .125 in. (3 mm) thick.

First, cut a 4-3/4in. (121 mm) diameter hole and three 1/4 in. (6 mm) diameter fastening holes as shown below. Insert the SWICHGAGE® from the back side of the panel. Using the three 10-24 screws, included with the SWICHGAGE®, secure to the panel.

Front View

4-3/4 in.

(121 mm) WIRING AND ADJUSTMENT INFORMATIONOne Thermocouple Only

5-1/2 in.

(140 mm)

Side View

4-1/4 in.

(108 mm)

Open Thermocouple InputMDTM89 Wiring and Adjustment Instructions 4 in. A.Using Thermocouple Extension Wire (102 mm)

Back View

 

Mounting Hole Pattern

Screw for

Remove Jumper(s)

 

 

4-3/4 in.

Equipment Ground

to Install

 

 

 

 

 

 

 

 

 

(121 mm)

 

Thermocouple

 

 

 

 

 

 

 

 

TC1

 

120

 

120

TC2

 

 

 

1/4 in.

 

 

(6 mm)

 

 

typical

 

2-39/64 in. radius

diameter

 

 

 

(66 mm)

 

WIRING AND ADJUSTMENT INFORMATION

CAUTION: Perform the wiring operation with the power source “OFF”. Make sure the voltage and current requirements are within the SWICHGAGE® ratings. Keep all high voltage wiring, such as spark plug wires away from THERMOCOUPLES

AND EXTENSION WIRING. Before wiring determine the voltage and polarity for the application.

One Thermocouple Only

Even though the MDTM89 is a dual temperature monitor, it will monitor and display one temperature with equal results.

When monitoring one temperature, always jumper the unused thermocou- ple terminals on the back of the MDTM89 with a short length of wire. The unused channel will display approximate ambient temperature.

Open Thermocouple Input

An open thermocouple input forces the monitor into upscale overrange. The monitor indicates an overrange by displaying the numeral “1” in the left most digit of the display. An overrange will turn on the trip point out- put, for the respective thermocouple.

MDTM89 Wiring and Adjustment Instructions

A.Using Thermocouple Extension Wire

1.After thermocouple installation, connect the thermocouple leads to

the MDTM89 according to the instructions. IMPORTANT: Use correct wire for the thermocouple selected.

USE ONLY THERMOCOUPLE EXTENSION WIRE.

2.If the thermocouple leads are not long enough you will need to use shielded thermocouple extension wire. The thermocouple extension wires, from your thermocouple lead wires to the terminals of the MDTM89, must be of the same material as the thermocouple lead wires. (See Table 1.)

Table 1. Thermocouple Extension Wire Color Code

 

 

 

 

Thermocouple

Thermocouple

Color Code/Material

Type

Extension Wire

Positive Lead

Negative Lead

 

 

 

 

J

Jx

White/Iron

Red/Constantan

 

 

 

 

K

Kx

Yellow/Chromel

Red/Alumel

 

 

 

 

Table 2. Thermocouple Extension Wire Loop Resistance in Ohms per Foot at 68°F

Size

 

 

 

 

 

 

Type “J”

 

 

Type “K”

 

AWG No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

.07

 

.146

 

 

 

 

 

 

 

16

 

.137

 

.230

 

 

 

 

 

 

 

18

 

.222

 

.374

 

 

 

 

 

 

 

20

 

.357

 

.586

 

 

 

 

 

 

 

24

 

.878

 

1.490

 

 

 

 

 

 

 

 

Thermocouple lead length: 150 ohm lead resis- tance affects monitor accuracy less than 1°.

MDTM-8907N page 2 of 4

Page 2
Image 2
Murphy One Thermocouple Only, Open Thermocouple Input, MDTM89 Wiring and Adjustment Instructions, Mounting Dimensions