Murphy specifications MDTM89 Interface Capabilities, Dual Temperature SWICHGAGE, Description

Models: MDTM89

1 4
Download 4 pages 28.06 Kb
Page 1
Image 1
Instructions for Installation and Operation Model Series MDTM89,

Instructions for Installation and Operation Model Series MDTM89,

Dual Temperature SWICHGAGE®

MDTM-8907N Revised 10-07 Section 10 (00-02-0165)

Please read the following information before installing. A visual inspection before mounting for any damage during shipping is recommended. General information and installation instructions are intended for all MDTM89 Series models.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCTDisconnect all electrical power to the machine.Make sure the machine cannot operate during installation.Follow all safety warnings of the machine manufacturer.Read and follow all installation instructions.

Description

Murphy's model MDTM89 is an electronic, dual-temperature moni- tor. It monitors two thermocouples, displays the temperature of the thermocouple selected, and has adjustable trip points for each input. A toggle switch provides for selection of the thermocouple to be dis- played and/or the temperature trip point to be checked/adjusted. If either trip point is reached, the associated output “turns on” and can be used as a control signal, or to initiate alarms and/or shutdown.

Specifications

Power Requirements (Operating Voltages):
MDTM89-A:100 to 350†† VDC, CD ignition, negative ground (FET outputs).

MDTM89-B:100 to 350†† VDC, CD ignition, negative or positive ground (SCR outputs).

MDTM89-C:12 to 24VDC, negative ground, 15 milliwatts (FET outputs).

MDTM89-D:120 VAC (MDTM89-C with 120 V isolation module #IT-1) (FET outputs.) Model NOT approved by CSA or Factory Mutual.

Power Consumption: CD ignition: 350 µa @ 100V; 120 VAC: 0.6 watts; 24 VDC: 0.5 watts.

Outputs: Model B: output turns on above trip point; output turns off when power is switched off; two (2) isolated SCR outputs, 0.5 amp @ 250 VDC.

Models A, C and D: output turns on above trip point; output turns off below trip point; two (2) isolated FET outputs, 0.5 amp @ 250 VDC.

Ambient Cold Junction Compensation Range:
32 to 122°F (1°C from 0 to 50°C).
Operating Temperature: -4 to 158°F (-20 to 70°C).

Dual Temperature SWICHGAGE®GENERAL INFORMATIONBEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT✔Disconnect all electrical power to the machine.✔Make sure the machine cannot operate during installation. ††

Storage Temperature: -40 to 300°F (-40 to 150°C).

Case: Die cast aluminum.

Reset Differential: FET models: Decreases 3 Degrees (°F or °C). SCR model: turn input power off to reset.

Measurement Range: Monitor Range 0-1999°F or °C (specify “F” or “C” in part number).

Accuracy: WithJ-type thermocouple: from 150-1200°F (66°-649°C) ±1.5% of reading. With K-type thermocouple: from 400-2000°F (204-1076°C) ±1.5% of reading. At calibration temperature.

Laboratory Approvals: CSAand Factory Mutual†† approved for Class I, Division 2, Group D, hazardous locations).

Thermocouple Lead Length: 150 ohm lead resistance affects moni- tor accuracy less than 1°.

Trip Point Accuracy: ±3°F (±2°C) of reading.
Trip Point Adjustment Range: 0-1999 Degrees.

MDTM89 Interface Capabilities

ModelPower SourceRating
LCDT

CD Ign., 120 VAC, 12/24 VDC

Cl.I, Div.1, Gr.D, Haz. areas*

S1400

120 VAC or 12/24 VDC

Cl.I, Div.1, Gr.D, Haz. areas*

MARK II and IV

CD Ignition, pos. or neg. grnd

Cl.I, Div.2, Gr.D, Haz. areas**

TATTLETALE®

CD Ign., 120 VAC, 12/24 VDC

Non-Hazardous areas

*An isolation barrier is needed between the MDTM89 and an Annunciator rated for Class I, Division 1, Group D, Hazardous Areas.

**When used with approved ignition. Contact Murphy for details.

When used with approved ignitions or 12-24 VDC. Contact Murphy for details.

††Approved for CD ignition, 80–250 VDC.

MDTM-8907N page 1 of 4

Page 1
Image 1
Murphy specifications MDTM89 Interface Capabilities, Instructions for Installation and Operation Model Series MDTM89