HAZARDOUS LOCATION INSTALLATION REQUIREMENTS

1.This equipment is suitable for use in Class I, Div 2, Groups A, B, C, and D, or unclassified or non- hazardous locations.

2.WARNING: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.

3.WARNING: Explosion hazard, do not disconnect while the circuit is live or unless the area is known to be non-hazardous.

4.WARNING: Explosion Hazard - Do not remove or replace the device unless power has been switched off or the area is known to be non-hazardous.

5.Use 60/75ºC rated Copper wire, (022Nm) 2 inch-lbs Tightening torque for field installed connectors.

6.WARNING: Install only in accordance with Local & National Codes of Authorities Having Jurisdiction.

7.Class I, Div 2 Installations require that power connections must be current limited at the power source with an in-line fuse rated at 0.5A.

8.Class I, Div 2 installations require that all devices connected to this product must be UL listed for the area in which it is installed.

9.Limited Operating Voltage: 12-30V for Class I, Div 2 installations.