FIGURE 6
10 FT.
3 FT.
MIN.
2 FT.
MIN.

6

THE TOTAL HORIZONTAL VENT LENGTH

PEDESTAL MODELS OUTSIDE AIR

SHOULD NOT EXCEED 40% OF THE CHIMNEY HEIGHT ABOVE THE STOVE.

All horizontal smoke pipe must slope slightly upwards a minimum of 1/4" per foot (6mm/ 0.3m) and all connections must be tight and secured by three sheet metal screws equally spaced.

If possible connect the air intake at the pedestal's back or bottom to the outside with a 4 inch (100mm) diameter fresh air kit available at your Napoleon/Wolf Steel Ltd. dealer. Follow detailed instructions under "Mobile Home Outside Air".

 

A"

 

B"

BASE

4.

PEDESTAL

5"

BELOW

 

 

AREA

FLOOR

STOVE

An uninsulated smoke pipe shall not pass through an attic, roof space, closet or simi- lar concealed space, or through a floor, ceil- ing, wall or partition, or any combustible con- struction.

DO NOT USE ANY MAKESHIFT MATERIALS DUR- ING INSTALLATION.

1.Move the stove into position with the flue centered, mid- point between two joists to prevent having to cut them. Use a plumb bob to line up the centre.

2.Cut and frame an opening in the roof to provide a 2" clearance between the outside of the chimney and any combustible material.

DO NOT FILL THIS SPACE WITH ANY TYPE OF

MATERIAL.

Nail headers between the joist for extra support. Firestop spacers must be placed on the bottom of each framed opening in any floor or ceiling that the chimney passes through.

3.Hold a plumb bob from the underside of the roof to determine where the opening in the roof should be. Cut and frame the roof opening to maintain proper 2" clear-

ances.

HEADERS

FIRESTOP SPACER -

FIGURE 5 UNDERSIDE OF JOIST

ADDING CHIMNEY SECTIONS

Add chimney sections, according

to the manufacturers installation instructions, securely, to the re- quired height. The chimney must extend, at least, 3 feet above its

point of contact with the roof and at least 2 feet higher than any wall,

roof or building within 10 feet. FIGURE 6. If your chimney system is enclosed within the attic area, a rafter radiation shield is required.

W415-0512 / B / 11.15.05

 

 

A (in.)

B(in.)

 

1100

8 5/8"

9 3/4"

FIGURE 7

1400

11 1/8"

9 3/4"

1900

14 7/8"

9 3/4"

 

WALL PASS-THROUGH

If possible, design the installa- tion so that the connector does not pass through a combustible wall. If during your installation you must pass through a combusti- ble wall, check with your build- ing inspector before you begin. Also check with the chimney con- nector manufacturer for any spe- cific requirements.

Consult with your dealer regard- FIGURE 8

ing special connection components available for use for wall pass-throughs.

Use only parts that have been tested and listed for use in a wall pass-through.

MOBILE HOME

PEDESTAL MODEL 1100 IS APPROVED FOR INSTAL- LATION IN MOBILE HOMES IN BOTH CANADA AND THE UNITED STATES.

1150 IS NOT APPROVED FOR MOBILE HOMES. PEDESTAL MODEL 1400 IS APPROVED FOR INSTAL- LATION IN MOBILE HOMES IN THE UNITED STATES ONLY.

WARNING: DO NOT INSTALL IN SLEEPING ROOM.

CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED.

BACK WALLBACK WALL

6"

 

WALL

45 °

WALL

 

 

2"

 

10"

SIDE

SIDE

 

 

 

FIGURE 9

 

 

FIGURE 10

 

The pedestal base must be firmly bolted to the floor with 1/ 4 inch lag bolts. Minimum clearances to combustibles are as shown in FIGURE 9.

VENTING

Connect the stove to a chimney system using a listed dou- ble wall connector. Use a chimney system listed to ULC S629 in Canada or UL103HT in the U.S.A.

The chimney must be installed in accordance with the manufacturer's instructions. Use only specified compo- nents with no substitutions. The chimney and pipe must extend at least 8 feet above the stove and 3 feet above the highest point of the roof. Install a rain cap at the top which will not impede the smoke exhaust. The chimney must be supported at the ceiling or roof so that its weight does not rest on the stove.

Page 6
Image 6
Napoleon Fireplaces 1400 Mobile Home, Pedestal Models Outside AIR, Adding Chimney Sections, Wall PASS-THROUGH, Venting