© National Instruments Corp. 11 cFP-RLY-421
Specifications
The following specifications are typical for a range of –40to 60°C
unless otherwise noted.

Relay Characteristics

Number of channels.......................... 8
Relay type......................................... 1 SPST, nonlatching
Maximum switching capacity (resistive load)
–40 to 60 °C
AC........................................ 1.5 A at 250 VAC
DC........................................ 1.5 A at 0 to 35 VDC
1A at 55 VDC
0.4 A at 120 VDC
Minimum switching load.................. 10 mA at 5 VDC
On resistance.....................................100 m
Off-state leakage (120 VDC/250 VAC)
Expected life
Mechanical............................ .....20 × 106 operations min
Electrical (at 30 cpm)................. 300,000 operations at 1.5 A,
35VDC;
100,000 operations at 1.5 A,
250 VAC
Maximum switching frequency
Mechanical.............................. ...20 operations per second
Electrical.....................................1 operation per second at
maximum load
Relays operate time...........................6 ms typical, 8 ms max
Relays release time.......................... .3 ms typical, 4 ms max
Relay bounce time....................... .....3 ms max
Contact material................................ Gold-plated silver cadmium
oxide
Frequency Off-State Leakage
DC 0.12 µA
50/60 Hz 8 µA