cFP-RLY-421 12 ni.com
Physical
Indicators....................... ...................Green POWER and
READY indicators, 8 green
output state indicators
Weight
cFP-RLY-421..............................130 g (4.5 oz)
Power Requirements
Power from network module............ 1,700 mW
Isolation Voltage
Maximum isolation voltage..............250 Vrms
Channel-to-channel isolation............No isolation between
channels
Transient overvoltage........................2,300 Vrms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature...................... –40 to 60 °C
Storage temperature..........................–55 to 85 °C
Humidity........................................... 10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered
Pollution Degree............................... 2
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64)..............................10–500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27)..............................50 g, 3 ms half sine,
18shocks at 6 orientations;
30 g, 11 ms half sine,
18shocks at 6 orientations