FP-CTR-502 and cFP-CTR-502 20 ni.com
Shock and VibrationThese specifications apply only to the cFP-CTR-502.
NIrecommends Compact FieldPoint if your application is
subjectto shock and vibration.
Operating vibration, random
(IEC 60068-2-64)..............................10–500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27)..............................50 g, 3 ms half sine,
18shocks at 6 orientations;
30 g, 11 ms half sine,
18shocks at 6 orientations
SafetyThis product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement,
control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to
the product label or to ni.com.
Electromagnetic CompatibilityCE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions..........................................EN 55011 Class A at 10 m
FCC Part 15A above 1GHz
Immunity...........................................EN 61326:1997 + A2:2001,
Table 1
Note For EMC compliance, you must operate this device
with shielded cabling.