© National Instruments Corp. 11 [c]FP-DO-403
Power RequirementsPower from network module............600 mW
Safety Isolation VoltageIsolation voltage is verified by a dielectric withstand test.
Channel to ground
Continuous................................. 250 Vrms, Measurement
Category II
Dielectric withstand....................2,300 Vrms, 5 s
Channel to channel.......... .................None
EnvironmentalFieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature
Input voltage ≤25 V....................–40 to 70 °C
Input voltage ≤30 V....................–40 to 50 °C
Storage temperature.......................... –45 to 85 °C
Humidity........................................... 10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m; at higher altitudes,
the isolation voltage ratings
must be lowered
Pollution Degree............................... 2
Shock and VibrationThese specifications apply only to the cFP-DO-403. NI
recommends Compact FieldPoint if your application is
subjectto shock and vibration.
Operating vibration, random
(IEC 60068-2-64)..............................10–500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27)..............................50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations