Appendix C SCXIbus Connector
© National Instruments Corporation C-3 SCXI-1163 User Manual
SCXIbus Connector Signal Descriptions
Pin Signal Name Description
A19 RESET* Reset – When pulled low, reinitializes the module to its
power-up state. Totem pole. Input.
B19 MISO Master-In-Slave-Out – Transmits data from the module
to the SCXIbus. Open collector. I/O.
C19 D*/A Data/Address – Indicates to the module whether
address information or data information is being sent to
the module on MOSI. Open collector. I/O.
D19 INTR* Interrupt – Active low. Causes data that is on MOSI to
be written to the Slot 0 Slot-Select Register. Open
collector. Output.
A21, B21, C21, CHSGND Chassis Ground – Digital and analog ground reference.
D21
A22, B22, C22, V+ Positive Analog Supply – +18.5 to +25 V.
D22
A23, D23 +5 V +5 VDC Source – Digital power supply.
B23 SPICLK Serial Peripheral Interface (SPI) Clock – Clocks the
serial data on the MOSI and MISO lines. Open
collector. I/O.
C23 MOSI Master-Out-Slave-In – Transmits data from the
SCXIbus to the module. Open collector. I/O.
B24 SS* Slot Select – When low, enables module
communications over the SCXIbus. Totem pole. Input.
* Indicates active low.
All other pins are not connected.
Further information is given in Chapter 3, Theory of Operation.