To Test Thermostat
emer heat off cool

110-1101 7/22/04 8:16 AM Page 6

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: DO NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY.

1. Place the EMER-HEAT-OFF-COOL switch into the COOL position. The emer heat off cool will be displayed.

2. Press the button until the temperature

emer heat off cool

setting is at least 3 degrees below the room

temperature. The air conditioning system should turn on within a few seconds.

NOTE: ONCE THE THERMOSTAT TURNS OFF WHEN IN THE COOL MODE, A BUILT IN 5-MINUTE DELAY PREVENTS THE SYSTEM FROM TURNING ON AGAIN. THIS PROTECTS THE COMPRESSOR. NO ADDITIONAL TIME DELAY RELAY IS REQUIRED. TO OVERRIDE THE

5-MINUTE DELAY FOR INSTALLATION, PRESS THE RESET BUTTON.

3. Put the EMER-HEAT-OFF-COOL switch into the OFF position. The air conditioning system should turn off.

 

 

emer heat off cool

4.

Put the EMER-HEAT-OFF-COOL switch into the

 

 

 

 

 

 

 

 

 

 

 

HEAT position. The will be displayed.

 

 

 

 

 

5.

Press the button until the temperature

 

 

 

 

 

emer heat off cool

 

setting is at least 3 degrees above room

temperature. The heating system should turn on. The fan may not turn on immediately, depending on the fan delay built into the furnace.

NOTE: If HP is selected, the heat will not come on until the 5 minute short cycle protection has expired.

6. Put the EMER-HEAT-OFF-COOL switch into the

EMER position. The 5-MINUTE DELAY FOR INSTALLATION, PRESS THE RESET BUTTON.auto on will be displayed.

7. Press the Manual background button until the temperature setting is at least 3 degrees above room

temperature. The secondary heating system should turn on.

NOTE: The compressor will not turn when in emergency heat mode.

8.

Put the EMER-HEAT-OFF-COOL switch into the

 

 

OFF position. The heating system should turn

 

 

off. The fan may continue to run for a short

 

 

period of time.

emer heat off cool

 

 

 

9.

Put the

AUTO-ON switch into the ON position.

 

The blower fan should turn on. The display will

 

 

show a

.

auto on

 

 

 

10.Put the Manual background AUTO-ON switch into the AUTO position. The blower fan should turn off.