TROUBLESHOOTING

TROUBLESHOOTING

PLEASE READ THIS SECTION BEFORE REFERENCING SPECIFIC DIAGNOSTIC MESSAGES.

1.Ensure the installation detail conforms with the recommendations contained in the Installation section of this manual.

2.Understanding the Principle of Operation is an asset when troubleshooting. A basic description

is provided in the section titled OPERATION. For a more detailed understanding please contact your NORTEC representative.

3.When contacting your local representative or NORTEC for troubleshooting assistance, please ensure the serial number has been obtained for reference purposes.

4.Whenever the troubleshooting steps indicate a problem with the main PCB, first check all connections at the main control board.

DIAGNOSTIC PROCEDURES - TROUBLESHOOTING

The RESDELUX controller provides a number of messages to simplify troubleshooting procedures. The following table presents fault messages displayed by the controller, their meaning and possible corrective actions. Refer to the following section for detailed information about terms used in the table.

Table #4 - Troubleshooting Guide

Unit Status Lamp

Symptom

Corrective actions

 

Yellow
Green

 

 

 

 

On

On

Maximum water level

This usually happens on initial start-up after replacing the cylinder

 

 

inside cylinder.

(normal).

 

 

 

 

Water is concentrated with minerals inside the cylinder.

 

 

 

 

Let unit run, yellow light will disappear when the unit is at full

 

 

 

output. This may take a day or two.

 

Off

Off

No power to the

Check for main power supply fault.

 

 

 

board.

Turn power switch to ‘Drain’ position. If drain valve is activated

 

 

 

(sound of solenoid), check connection to the board or board itself.

 

 

 

When no sound present, check fuse (replace with 1.5A if needed),

 

 

 

transformer (voltage should be present between fuse holder and

 

 

 

ground screw).

 

1 flash

Off

Over current.

Check drain valve operation, drain time, possible drain

restrictions.

sequence

 

Operating amperage

Check if fill valve leaks (not holding supply water).

 

 

 

exceeded 130% of

Back pressure may also cause very conductive water

conditions.

 

 

rated amps. Water is

 

 

Was the humidifier short cycling?

 

 

 

drained from the

 

 

 

Check for short cycling.

 

 

 

cylinder (drain valve

 

 

 

 

 

 

 

on for 10 min.).

 

 

2 flashes in

Off

No current

Check water level in the cylinder - should be more than ¼ full. If not

sequence

 

detection for 30

check fill rate, 24 VAC voltage on fill valve terminals (unit must be

 

 

minutes with

on with call for humidity - green light steady on). Verify fresh water

 

 

continuous call for

supply to the humidifier. Leaking drain valve can be at fault

 

 

humidity.

(minerals blocking the plunger).

 

 

 

 

If cylinder is more than ¼ full, check primary power, connections to

 

 

 

the cylinder, continuity of wires to cylinder.

 

 

 

 

Are power wires connected to proper terminals on the cylinder?

 

 

 

(Color coding)

 

 

 

 

Possibly wrong cylinder type.

 

 

 

 

Low water conductivity.

 

4 flashes in

Off

End of cylinder life -

Check water level in the cylinder, should be about ¾ full.

sequence

 

change cylinder.

Check for foaming if water level lower or cylinder life shorter than

 

 

 

expected.

 

 

 

 

Change cylinder, clean drain valve.

 

 

 

 

 

 