Nortec BSD, ASD, CSD H 1/3W 1/3W 1/3W, 1/3W 2/3W, Min. W = 8” 203 mm, Figure #5 Vertical Airflow

Models: BSD CSD ASD

1 12
Download 12 pages 5.18 Kb
Page 8
Image 8
Figure #5

Figure #5

Vertical Airflow

C2

Always align distributor holes so that steam is discharged upwards to ensure condensate will remain in the distributor.

W

1/3W 1/3W  2/3WHMin. W = 8” (203 mm) 2/3W

H

1/3W 1/3W 1/3W

Min. W = 8” (203 mm)

GO TO D

WARNING:

￿These installation guidelines apply for duct velocities under 2000 ft/min (610 m/min), please consult factory for higher velocities.

￿Please make sure no obstacles (elbow, filter, or diffuser) are located after the distributor in the direction of the airflow closer than the absorption distance calculated for your application.

￿Unless you know the exact absorption distance required for the steam absorption into the air stream, the distributor should be located at least 8-10 ft (2-3 m) away from any obstacle it may condense on (elbow, diffuser, filter, etc.).