Nortec CSD, ASD Condensate Return Guidelines For Main Steam Lines, Full Size, Drain Tee, Chart #3

Models: BSD CSD ASD

1 12
Download 12 pages 5.18 Kb
Page 4
Image 4
Chart #3

Chart #3

Recommended Condensate line at distributor(s)

Dispersion

Condensate

Copper tube

Stainless Steel

Method

Hose

tube

 

 

 

 

 

1 x Steam

3/8" Nortec

1/4" MED-L

3/8” tube

Tubing

distributor

1328840

0.049” thick.

(3/8" O.D.)

 

 

 

3 x Steam

3/8" Nortec

1/2" MED-L

5/8” tube

Tubing

Distributor*

1328840

0.049" thick

(7/8" O.D.)

 

 

 

*When using more than one distributor, the condensate line should be trapped before joined together.

CONDENSATE RETURN GUIDELINES FOR

MAIN STEAM LINES

1.Use vertical condensate leg of distributor only. Do not over-tighten clamp.

2.Drip stations on steam mains must be located at all low points in the system, at each elevation change and or directional change.

3.Horizontal runs of steam must have a 2” rise per foot (10º) when flow is going upwards from drip station and the steam run is to fall ½” per foot (2º) when flow is going downwards to drip station.

4.In a horizontal run of the steam main, drip stations must be located at regular intervals of 20 feet.

5.The drip station itself is a section of piping connected to the bottom of the main. A full size tee must be used to create a drip station to allow the condensate to fall in the drip station.

Figure #1

Drain Tee

Full Size

Drain Tee

6.Vertical drop of the drip station should be 1.5 times the diameter of the steam main but no less then 12”.

7.At the bottom of this drip station is where the “p-trap” is installed. It is to be 2” larger then the duct static duct pressure.

8.All distributors must be individually trapped.

- 2 -

Page 4
Image 4
Nortec CSD, ASD, BSD Condensate Return Guidelines For Main Steam Lines, Full Size, Chart #3, Figure #1 Drain Tee