-20-
5. Remove locking screws on the front of the Scale
T
ank support
mechanism.
Scale tank last replaced on:
ON
OFFDRAIN
12
6
PN: 150-5913 Rev.A
7. Visually inspect cylinder, heating elements and o-ring. Clean or
replace if necessary.
6. Lower and remove Scale Tank.
4. Disconnect hose connection on scale tank.
3. Open manual drain valve on Scale Tankto drain remaining
water
2. Turn off the unit.
1. Drain Cylinder.
ScaleCollectorTankSCALE COLLECTOR TANK SERVICING
Note: Scale collector tank has to be removed after 5000 hours
or 3 years, whichever comes first.