NT-8101-HI-TX

. 8 single-ended 4-20 mA input channels

. Non-incendive field circuits

. HART pass-through

. HART variable and status reporting

. 2- or 4-wire transmitters

. open and short circuit detection

. 24 V dc bussed field power required

Module Specifications

 

 

 

Inputs

 

 

 

Number of channels

8, single-ended

Nominal signal range (span)

4 to 20 mA

Full signal range

1 to 23 mA

Line fault detection

 

 

 

 

 

Short circuit current

> 23.5 mA

 

 

Open circuit current

< 0.5 mA

Output voltage (@ 20mA)

13.5 V (min.)

Output current

32 mA (max.)

Accuracy (over temp range)

± 0.1% of span

Resolution

16 bits

Repeatability

0.05% of span

Isolation

 

 

 

 

 

(any channel to Railbus)

100 V ac

 

 

(between channels)

none

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks are properties of their respective owners. NovaTech is a registered trademark of NovaTech, LLC. The information in this literature is subject to change without notice and is not to be construed as a warranty. DS_8101_0607

8 Channel Analog Input

4–20 mA with HART®

NovaTech 8000 Series I/O Family

Configurable Parameters

 

 

Input filter time constant

.................................

user defined value

Input dead zone

user defined value

Drive on failsafe

disabled /upscale /downscale

Channel status

active /inactive

Image Description

...................

enable /disable

HART variable and status reporting

Response Time

 

 

Signal change to availability on Railbus

 

4–20 mA mode

27 ms (max.)

HART mode

0.75 s per channel

Safety

FM non-incendive field wiring parameters (each channel) Voc = 28.7 V; Isc = 33 mA; Ca = 0.17 µF; La = 11.0 mH

 

Power Supplies

 

 

 

 

 

Railbus (12V) current

100 mA (typ.), 150 mA (max.)

 

Bussed Field Power 2-wire Tx

300 mA (max.)

 

(@ 24 V dc ±10%) 4-wire Tx

60 mA (max.)

 

Mechanical

 

 

 

 

 

Module Key Code

 

 

A1

 

Module width

 

 

42 mm

 

Weight

 

 

200 g

 

Field Terminals (2-WIRE TX)

 

 

 

 

 

 

 

 

Field Wiring

Recommended

Compatible

 

 

Field Terminal

Field Terminal

 

General Purpose

NT-8602-FT-ST

NT-8604-FT-FU

 

 

Standard

Fused

 

 

 

 

 

Class 1, Div 2

NT-8601-FT-NI

NT-8603-FT-FU

 

or Zone 2 hazard-

Non-incendive

Non-incendive

 

ous area

 

 

 

 

 

 

 

 

 

 

 

Field Terminals (4-WIRE TX)

 

 

 

 

 

 

 

 

Field Wiring

Recommended

Compatible

 

 

Field Terminal

Field Terminal

 

General Purpose

NT-8615-FT-4W

-

 

 

 

 

 

 

 

Class 1, Div 2

NT-8615-FT-4W

-

 

 

or Zone 2 hazard-

 

 

 

 

 

ous area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact:

 

T: 410.753.8300

 

NovaTech Process Solutions, LLC

 

11500 Cronridge Dr., Suite 110

Toll Free: 800.253.3842

 

Owings Mills, MD 21117

www.novatechweb.com

 

 

 

 

 

 

Page 8
Image 8
NotaTech 8000SeriesI/O manual NT-8101-HI-TX, MA with Hart

8000SeriesI/O specifications

The NotaTech 8000 Series I/O is a cutting-edge technology designed to revolutionize industrial automation and process control systems. As industries increasingly seek to enhance productivity and efficiency, the 8000 Series I/O steps up by providing a robust and flexible interface to integrate various sensors, actuators, and controllers.

One of the standout features of the NotaTech 8000 Series I/O is its modular design. This allows users to customize their I/O configuration according to the specific requirements of their applications. With a range of modules available, including digital, analog, and specialty I/O, users can easily scale their systems to meet evolving demands.

Another key characteristic of the 8000 Series I/O is its high-speed data communication capabilities. Utilizing advanced protocols such as EtherCAT, PROFINET, and Ethernet/IP, the system ensures rapid data transfer between devices, significantly reducing latency in control loops. This high-speed communication supports real-time performance, making it ideal for time-sensitive applications.

The NotaTech 8000 Series also boasts an impressive level of reliability and durability. Engineered for harsh industrial environments, the modules are built to withstand extreme temperatures, vibrations, and humidity. IP ratings ensure protection against dust and water ingress, contributing to prolonged operational life and minimal downtime.

Incorporating state-of-the-art diagnostics, the 8000 Series I/O provides comprehensive monitoring of system health. Users can access diagnostic data through user-friendly interfaces, allowing for proactive maintenance and troubleshooting. This feature not only reduces maintenance costs but also enhances the overall system reliability.

Another notable technology integrated into the NotaTech 8000 Series is its support for various fieldbus systems. With multi-protocol support, users can connect easily to existing infrastructure without the need for system overhauls. This flexibility promotes interoperability and eases upgrades as technology evolves.

Security is paramount in industrial environments, and the NotaTech 8000 Series I/O addresses this with built-in cybersecurity features. These include secure communication channels and access controls, safeguarding against potential cyber threats and ensuring data integrity.

In summary, the NotaTech 8000 Series I/O stands out in industrial automation for its modular adaptability, high-speed communication protocols, rugged design, advanced diagnostics, multi-protocol support, and a strong focus on cybersecurity. As industries continue to innovate and evolve, the 8000 Series I/O positions itself as a vital component in the quest for increased efficiency and reliability in automation systems.