WARNING
TO REDUCE THE RISK OF FIRE, ELEC- TRIC SHOCK, OR INJURYTO PERSONS, OBSERVE THE FOLLOWING:
1.Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2.Before servicing or cleaning unit, switch power off at service panel and lock the ser- vice disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3.Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4.Sufficient air is needed for proper combus- tion and exhausting of gases through the flue (chimney) of fuel burning equipment to preventbackdrafting.Followtheheatingequip- ment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Re- frigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5.When cutting or drilling into wall or ceiling, do notdamageelectricalwiringandotherhidden utilities.
6.Ducted fans must always be vented to the outdoors.
7.Acceptableforuseoveratuborshowerwhen connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
8.This unit must be grounded.
CAUTION
1.For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2.This product is designed for installation in flat ceilings only.DO NOT MOUNTTHIS PROD-
UCT IN A WALL.
3.To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4.Please read specification label on product for further information and requirements.
Installer: Leave this manual
with the homeowner.
OPERATION
The humidity control and fan can be op- erated separately. Use a 1 or 2-function wall control. Do not use a dimmer switch to operate the humidity control or light. See “Connect Wiring” for details.
SENSOR OPERATION
This humidity-sensing fan responds to: (a) rapid to moderate humidity increases and
(b)humidity above a 50%-80% relative humidity (RH) set-point. (a) and (b) are set with “HUMIDITY” adjustment. Fan may occasionally turn on when environmental conditions change. If the fan continuously responds to changing environmental con- ditions, “HUMIDITY” adjustment may be required (see section below).
STATUS INDICATOR
This indicator can only be seen by looking directly at it. Normal mode is 5-seconds on and off. If it blinks rapidly for 5-seconds and then off, check sensor connections on grille and fan housing.
MANUAL ON WITH TIMED OFF
For odor or vapor control, the fan can be energized by cycling its wall-mounted switch if one is installed. Once the fan has been turned on in this manner, it will remain on for the set “MINUTES” period.
To manually energize the fan:
1.Go to Step 2 if switch is already on; otherwise, turn switch on for more than 1 second.
2.Switch off for less than 1 second.
3.Switch back on and fan will turn on.
HUMIDITY ADJUSTMENT
“HUMIDITY” has been factory set for most shower applications. If the fan is in a tub area or is used for dampness control, the “HUMIDITY” may need to be decreased toward 50% RH. If the control is responding too often to changing environmental condi- tions, adjustment toward 80% RH may be required. To adjust the “HUMIDITY”:
1.Turn power off at electrical service panel.
2.Through the grille, locate the “HUMIDITY” screwdriver slot.
3.Using a small, flat-blade screwdriver, carefully rotate “HUMIDITY” adjustment toward 50 or 80.
4.Turn power on and check operation by turning on shower or other humidity source until fan turns on.
5.Repeat above steps if necessary.
TIMER ADJUSTMENT
This humidity-sensing fan has a timer. It is user-adjustable from 5 to 60 minutes and is factory-set at 20 minutes.The timer controls how long the fan remains on (a) after rise in humidity and (b) humidity level are both below the user-adjustable “HUMIDITY” setting or after being energized by cycling power switch.
To adjust the timer:
1.Disconnect power at electrical service panel.
2.Through the grille, locate the “MINUTES” screwdriver slot.
3.Using a small, flat-blade screwdriver, carefully rotate “MINUTES” adjustment to desired setting (5 to 60 minutes).
4.Check operation by cycling power switch as instructed under “MANUAL ON WITH TIMED OFF” or by turning on a humidity source until fan turns on.
5.Check timer setting with watch or clock after turning humidity source off if it was turned on it Step 4.
6.Repeat above steps if necessary.
CLEANING & MAINTENANCE
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor/blower wheel assembly.
SENSOR CLEANING
The humidity sensor is mounted in the grille. The sensor will operate most reliably when cleaned occasionally as follows:
1.Disconnect power at service entrance.
2.Remove the grille. Use a dry dustcloth, clean toothbrush, or lightly vacuum to clean sensor and grille. DO NOT USE ABRASIVE CLOTH, STEEL WOOL PADS, OR SCOURING POWDERS.
3.DO NOT USE cleaning sprays, solvents, or water on or near the sensor!