4-4. Instruction for screen change and each screen

Note: In the following, the

mark

ENT key

indicates that the key above

5 seconds

the mark should be pressed.

 

MODE 1 Screen Group

Mode 0 Screen Group

key

 

3 seconds

0-0

 

Basic screen

 

SV initial value:

lower limit of measuring range

Setting range:

within measuring range

Upper row displays measured value (PV) and lower row displays and changes the set value (SV). Refer to Item 5-1 for detail.

0-1

1-0

1-1

Direct call screen (screen No.0)

Initial value: 0

Setting range: 0~19

Set the screen No. to move the screen of the mode 1 screen group. Refer to Item 4-3 (4) for detail.

The screen with no display condition is skipped.

Set value bias set screen (screen No.1)

Initial value: 0

Setting range: -1999~2000 unit

0-2

Control output screen

Initial value for manual operation:

The value immediately before switched to manual Setting range for manual operation: 0~100%

The measured value (PV) is displayed on the top and the control output value on the bottom. Pressing the MAN key on this screen switches auto to manual and vice versa. Refer to Item 4-6 (1) for detail.

Control execution/stop selecting screen

Initial value:

EXEC

Setting range:

EXEC, STBY

1-2

P OFF

Displays in the case with set value bias option. The set value is effective during shorted SB terminal, and is added to the set value. While it is valid, the leftmost point on the bottom row stays lit on each displayed screen, excluding the input scaling setting screen.

Proportional band set screen (screen No.2)

Initial value: 3.0%

Setting range: OFF, 0.1~999.9%

Refer to Item 6-2 (1) for proportional band.

Select “OFF” to perform ON/OFF action.

STBY, MAN, For ON/OFF

0-3

Execution (

) or stop (

) of control is selected.

Refer to Item 4-6 (2) for detail.

P=OFF

1-3

Action hysteresis set screen (screen No.3)

Initial value: 3 or 0.3

 

 

AT (auto tuning) action control screen

 

 

Initial value: OFF

 

 

Setting range: OFF, ON

 

 

For “ON” selection, AT is executed and for “OFF” selection, AT is

 

 

cancelled.

No option

Refer to Item 5-2 for detail. This screen appears only during ON/OFF

operation; it does not appear when control is suspended or during

 

 

0-4

manual output.

Higher limit alarm set screen

 

 

Setting range: 1~999 unit

Set ON/OFF hysteresis on ON/OFF action.

This screen appears only when P=OFF.

1-4

Integral time set screen (screen No.4)

Initial value: 120 seconds

Setting range: OFF, 1~6000 seconds Refer to Item 6-2 (2) for integral time.

Not shown on ON/OFF action. Selection of OFF starts P or PD action.

1-5

Initial value:

Absolute value alarm:

 

higher limit for the measuring range

 

Deviation alarm: 2000 unit

Setting range:

Absolute value alarm: within measuring range

 

Deviation alarm: 0~2000 unit

Displays except the case with alarm option and the alarm type of the

function selecting screen of mode 2 screen group is not specified.

Refer to Item 5-3 (1) for detail.

0-5

 

Lower limit alarm set screen

Initial value:

Absolute value alarm:

 

lower limit for the measuring range

 

Deviation alarm: -1999 unit

Setting range:

Absolute value alarm: within measuring range

 

Deviation alarm: -1999~0 unit

Displays in case with alarm option and the alarm type of the function selecting screen of mode 2 screen group is higher limit and lower limit. Refer to Item 5-3 (2) for detail.

0-6

Heater break alarm value set screen

Initial value: OFF

Setting range: OFF, 0, 1~50.0A or OFF, 1~500A

Displays in the case with heater break alarm option and alarm type of the mode 2 screen is higher limit+heater break.

Refer to Item 5-3 (3) for detail.

Upper row displays load current detected by CT.

(If the output is OFF, it shows

 

 

 

 

 

 

 

 

 

)

 

 

 

 

 

 

 

 

 

NOTE: The heater break alarm can be added if the instrument has alarm option and the control output is the contact type or the SSR drive voltage type.

Heater break alarm

Set the alarm level at approx. 85% of the normal load current. In case of large current variation, set larger value.

If multiple heaters are connected in parallel, set a larger value to output alarm for single heater

break.

• If “ ” is selected, no alarm output is obtained. Selecting “ ” during alarm output, the alarm output is canceled.

For case when heater break function is not applicable to direct current load, phase controlling

 

current and three phase heater.

Connecting current transformer (CT)

I OFF

I=OFF

1-6

1-7

1-8

1-9

1-10

Derivative time set screen (screen No.5)

Initial value: 30 seconds

Setting range: OFF, 1~3600 seconds

Refer to Item 6-2 (3) for derivative time.

Not shown on ON/OFF action.

Selection of OFF starts P or PI action.

Manual reset value setting screen (screen No.6)

No.6 Initial value: 0.0%

Setting range: -50.0~-50.0%

Offset is adjusted when I=OFF (P or PD action) is selected. For details of manual resetting, refer to Item 4-6 (3).

This screen appears only when 1=OFF has been selected.

Set value function set screen (screen No.7)

Initial value: 0.40

Setting range: OFF, 0.01~1.00

Used for suppressing overshooting and undershooting in expert PID. For SF=1.00, minimize overshooting, for SF=OFF, expert PID is unable to be normal PID action. This screen does not appear when P=OFF or I=OFF.

PV bias value set screen (screen No.8)

Initial value: 0 or 0.0

Setting range: -200~200 unit

Used for sensor input error compensation.

Controlling is performed with corrected value for bias setting.

PV filter time set screen (screen No.9)

Initial value: 0 second

Setting range: 0~100 seconds

Used for the case of large input change and noise overlapping to reduce the effect.

Key lock mode set screen (screen No.10)

Initial value: OFF

Setting range: OFF, 1, 2, 3

No data change is effective on the display screen locked.

Nevertheless, the direct call screen and the keylock mode setting screen are not locked by setting any lock No.

One of the load line wires passes through the hole of the custom CT.

Wire from the secondary side terminal of CT to the CT input terminal of the instrument.

To CT input terminal of

NOTE: Two types of the heater break

controller (no polarity)

CT of 30A and 50A are available, the

 

 

type selected upon ordering is shipped

 

with the product as an accessory. Note

 

the maximum current to be set is 50.0A

Heater (load) wire

for both types. CT is not provided when

 

0~500A is designated.

 

 

Lock Nos. and Ranges to be locked are as follows:

Lock No.

Range of Screens to Be Locked

OFF

Release of lock

1Other screens than basic, control output,

AT action control and communication mode screens

2All except basic screen

3All screens

- 6 -

Page 8
Image 8
Omega CN154, CN155, CN158, CN159 manual Instruction for screen change and each screen, Basic screen

CN159, CN155, CN158, CN154 specifications

Omega watches have long been celebrated for their precision, durability, and innovative features, and models such as the CN154, CN158, CN155, and CN159 exemplify these qualities. Each of these timepieces showcases Omega's commitment to craftsmanship and cutting-edge technology.

The Omega CN154 model is notable for its sleek design, combining elegance with robust functionality. Its stainless-steel case ensures durability while maintaining a lightweight feel. The watch features a mesmerizing sapphire crystal that provides scratch resistance and enhances visibility, allowing wearers to appreciate the intricate dial details. Equipped with Omega's Co-Axial escapement technology, the CN154 offers exceptional accuracy and reduced friction, resulting in a longer service life.

Similarly, the Omega CN158 stands out with its distinctive aesthetic and advanced technical features. This model incorporates the brand's renowned chronometer certification, guaranteeing its precision. The CN158 utilizes a helium escape valve, an essential feature for professional divers, enabling it to withstand high pressures during underwater activities. The luminous hands and markers ensure visibility in low-light environments, making it ideal for both diving adventures and everyday wear.

The CN155 model focuses on functionality without compromising style. Its tachymetric scale on the bezel allows for precise speed calculations, catering to motorsport enthusiasts. The chronograph feature provides accurate timing capabilities, while the stainless-steel bracelet offers comfort and security. The watch's water resistance up to 300 meters enhances its versatility, making it a reliable companion for any occasion, be it a business meeting or an ocean dive.

Lastly, the Omega CN159 encapsulates luxury and performance. With a striking ceramic bezel and an intricately designed dial, this timepiece makes a bold statement. The CN159 is equipped with Omega's Master Chronometer technology, which ensures precision while also being resistant to magnetic interference. This allows it to maintain accuracy even in environments with strong magnetic fields. The watch also features a transparent case back, showcasing the exquisite craftsmanship of the automatic movement within.

In summary, the Omega CN154, CN158, CN155, and CN159 models represent the pinnacle of watchmaking innovation. They combine style, precision, and advanced technologies, making them excellent choices for discerning watch enthusiasts. Whether for professional use or personal style, these timepieces offer something for everyone, ensuring Omega remains a leader in the luxury watch industry.