SECTION 13. SPECIFICATIONS (continued)

ALARM OUTPUTS

2 Form "C" on/off relays. Configurable for latched and

(if applicable)

unlatched by software.

 

 

Max current: 5 AMPS, resistive load

 

 

Max voltage: 250 Vac or 30 Vdc

ENVIRONMENT

 

~ AC units

115/230 V~(AC) + 10%, 50/60 Hz

 

 

7 W max, power consumption (Non-Isolated Analog Out)

 

 

8 W max, power consumption (Isolated Analog Out)

 

DC units

10-32 Vdc or 26-56 Vdc,

 

 

 

6 W max, power consumption (Non-Isolated Analog Out)

 

 

7 W max, power consumption (Isolated Analog Out)

External Fuse Required:

 

 

 

 

 

IEC 127-2/III

 

 

 

 

 

 

Power

 

Fuse

 

115 V

 

125 mA @ 250 (T)

 

 

 

 

 

230 V

 

63 mA @ 250 (T)

 

UL 248-14 (Listed Fuse)

 

 

 

 

Power

 

Fuse

 

115 V

 

175 mA @ 250 V Slow-Blow

 

230 V

 

80 mA @ 250 V Slow-Blow

 

 

 

 

ENVIRONMENT

 

Operating temperature:

0° to 50°C (32° to 122°F)

 

(115/230 V rms + 10%)

Storage temperature:

-40° to 85°C (-40° to 185° F)

Relative humidity:

90% at 40°C (non-condensing)

MECHANICAL

 

Panel cutout:

1/8 DIN 3.62 x 1.78" (45 x 92mm)

Weight:

1.27 lb (575 g)

Case material:

Polycarbonate, 94 V-O UL rated

Protection:

NEMA-4/Type 4 Front BezeL