7
5.0 CONFIGURATION
The standard TX82B meter is factory-configured for an input of 4-20 mA to display
00.0 to 100.0. Field configuration for input current range, decimal point location,
dummy right-hand zero digit, coarse zero range selection, and reverse span slope
may be done by relocating internal push-on jumpers and adjusting the span and
zero potentiometers. Refer to Figure 5-1 for the span and zero potentiometers and
internal jumper locations.
5.1 STANDARD SETUP
Unless the customized configuration option is specified, jumpers are factory-installed
at S1-H, S2-C, S1-B, S1-C and the unit is calibrated for 4-20 mA = 00.0 to 100.0.
5.2 FIELD CONFIGURATION CHART
CONFIGURATION JUMPER INSTALLATION
1.5 mAInput None
*4-20 mAInput S1-H
10-50 mAInput S1-J
*Normal Span Slope S1-B, S1-C
Reverse Span Slope S1-A, S1-D
Decimal Point 1.999 (DP1) S2-E
Decimal Point 19.99 (DP2) S2-D
*Decimal Point 199.9 (DP3) S2-C
Decimal Point 1999. (DP4) S2-B
Decimal Point 19990. (DP5) S2-F
Dummy Right-Hand Zero (DRHZ) S2-A
Dummy Right-Hand Zeroes (2DRHZ) S2-G, S2-H, S2-J, S2-A
Zero Range -2510 to -1420 (ZR1) S1-G
Zero Range -1580 to -420 (ZR2) S1-F
*Zero Range -470 to +850 (ZR3) None
Zero Range +760 to +2000 (ZR4) S1-E
*Standard factory setup