402

11-1 Communications Procedure

Command Chart The commands listed in the chart below can be used for host link communica-

tions with the C200HS. These commands are all sent from the host computer to

the PC.

Header code PC mode Name Page
RUN MON PRG
g
RR Valid Valid Valid IR/SR AREA READ 407
RL Valid Valid Valid LR AREA READ 407
RH Valid Valid Valid HR AREA READ 408
RC Valid Valid Valid PV READ 408
RG Valid Valid Valid TC STATUS READ 409
RD Valid Valid Valid DM AREA READ 409
RJ Valid Valid Valid AR AREA READ 410
WR Not valid Valid Valid IR/SR AREA WRITE 410
WL Not valid Valid Valid LR AREA WRITE 411
WH Not valid Valid Valid HR AREA WRITE 411
WC Not valid Valid Valid PV WRITE 412
WG Not valid Valid Valid TC STATUS WRITE 412
WD Not valid Valid Valid DM AREA WRITE 413
WJ Not valid Valid Valid AR AREA WRITE 413
R# Valid Valid Valid SV READ 1 414
R$ Valid Valid Valid SV READ 2 415
R% Valid Valid Valid SV READ 3 416
W# Not valid Valid Valid SV CHANGE 1 417
W$ Not valid Valid Valid SV CHANGE 2 417
W% Not valid Valid Valid SV CHANGE 3 418
MS Valid Valid Valid STATUS READ 419
SC Valid Valid Valid STATUS WRITE 420
MF Valid Valid Valid ERROR READ 421
KS Not valid Valid Valid FORCED SET 422
KR Not valid Valid Valid FORCED RESET 423
FK Not valid Valid Valid MULTIPLE FORCED SET/RESET 424
KC Not valid Valid Valid FORCED SET/RESET CANCEL 425
MM Valid Valid Valid PC MODEL READ 425
TS Valid Valid Valid TEST 426
RP Valid Valid Valid PROGRAM READ 426
WP Not valid Not valid Valid PROGRAM WRITE 427
MI Not valid Not valid Valid I/O TABLE GENERATE 427
QQ Valid Valid Valid COMPOUND COMMAND 427
XZ Valid Valid Valid ABORT (command only) 429
:: Valid Valid Valid INITIALIZE (command only) 430
IC --- --- --- Undefined command (response only) 430

Communications Procedure Section 11-1