423
Parameters Name, Word address, Bit (Command)
In “Name”, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced
set. Specify the name in four characters. In “Word address”, specify the address
of the word, and in “Bit” the number of the bit that is to be forced set.
Name Classification Word address setting Bit
OP1 OP2 OP3 OP4
g
range
C I O (S) IR or SR 0000 to 0511 00 to 15 (decimal)
L R (S) (S) LR 0000 to 0063
()
H R (S) (S) HR 0000 to 0099
A R (S) (S) AR 0000 to 0027
T I M (S) Completion Flag (timer) 0000 to 0511 Always 00.
T I M H Completion Flag (high-speed timer)
y
C N T (S) Completion Flag (counter)
C N T R Completion Flag (reversible counter)
T T I M Completion Flag (totalizing timer)
(S): Space
Note 1. The area specified under “Name” must be in four characters. Fill any gaps
with spaces to make a total of four characters.
2. Words 253 to 255 cannot be set when the CIO Area is specified.
11-3-25FORCED RESET –– KR
Force resets a bit in an IR, SR, LR, HR, AR, or TC area. Once a bit has been
forced set or reset, that status will be retained until FORCED SET/RESET CAN-
CEL (KC) is transmitted.
Command Format
@KR
x 100
x 101x 103x 102x 101x 100x 101x 100:
OP1 OP2 OP3 OP4
Node no. Header
code TerminatorFCS
Name Word
address Bit
Response Format
@KR
x 100
x 101x 161x 160:
Node no. Header
code TerminatorFCSEnd code
Parameters Name, Word address, Bit (Command)
In “Name”, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced
reset. Specify the name in four characters. In “Word address”, specify the ad-
dress of the word, and in “Bit” the number of the bit that is to be forced reset.
Name Classification Word address setting Bit
OP1 OP2 OP3 OP4
g
range
C I O (S) IR or SR 0000 to 0511 00 to 15 (decimal)
L R (S) (S) LR 0000 to 0063
()
H R (S) (S) HR 0000 to 0099
A R (S) (S) AR 0000 to 0027
T I M (S) Completion Flag (timer) 0000 to 0511 Always 00.
T I M H Completion Flag (high-speed timer)
y
C N T (S) Completion Flag (counter)
C N T R Completion Flag (reversible counter)
T T I M Completion Flag (totalizing timer)
(S): Space
Host Link Commands Section 11-3