Fire alarm systems
External Presentation unit
1728
•For presentation of
•Compact size
Presentation unit 1728
This unit (S/W V1.2) is intended for pre- warning, fire and heavy smoke / heat alarm
presentation. Point or zone alarm presentation is like in the c.i.e. it is connected to. You can scroll amongst two or more alarms in the system but the fire alarms can not be reset via this unit. All or selected alarms will be presented in a display (LCD, 2x40 characters with back- light). An alarm text will be presented together with each alarm, if programmed in the c.i.e. Furthermore, >617 texts for selected alarms can be stored in the unit and will in such a case be shown, instead of the texts sent from the c.i.e. for these alarms. A
LEDs, push buttons etc.
The unit has the following LEDs:
•Fire (Brand) and Alarms queued (Flera larm), indicating
•Operation (Drift), indicating that the unit is connected to a c.i.e. and power supplied, i.e. it is in operation.
•Extinguishing (Släckanläggning aktiverad), indicating activated output for extinguishing equipment.
• | Ventilation | (Brandventilation |
| aktiverad), indicating | activated output |
| for ventilation equipment. |
•Fire brigade tx (Larmsändare aktiverad), indicating activated output for Fire brigade tx (routing equipment).
The unit has the following push buttons:
•Alarms queued (Flera larm), used to scroll amongst the alarms.
•Silence buzzer (Summer tyst), used to silence the buzzer (it will
The designation texts on the front are in 1728SE in Swedish and in 1728UK in English.
Compact size
The compact size enclosure is made of grey high impact ABS. Fitted with a supple- mentary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The push buttons on the front are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached.
SW mode and address setting
The display and the push buttons are used to set the SW mode and address, see the opposite side of this page.
Product application
The 1728 unit is intended for indoor use and in dry premises. SW mode 1728 - 1587 is intended to be used in the systems EBL512 and EBL128 and SW mode 1728 – 1582 in the systems EBL500 / 512 / 1000 / 2000.