Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart
(2) Operating current performance chart
(3) Indoor discharge air performance chart
This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
The performance is for a tubing length of 24.6t (7.5m). If the tubing length is different, the performance chart will vary.
NOTE
Low pressure at wide tube service valve
psig (MPaG)
Outdoor air temperature °F (°C)
174
(1.2)
188
(1.3)
160
(1.1)
146
(1.0)77
(25) 86
(30) 95
(35) 104
(40)
Lo fan Hi fan HH fan
Operating current (A)
Outdoor air temperature °F (°C)
4
5
3
2
Lo fan Hi fan HH fan
Indoor discharge air temperature °F (°C)
Outdoor air temperature °F (°C)
46.4( 8)
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Lo fan Hi fan HH fan
Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS7NKU ×1

5-1-1. Temperature Charts (CU-3KS19NBU)

77
(25) 86
(30) 95
(35) 104
(40)
77
(25) 86
(30) 95
(35) 104
(40)

5. PERFORMANCE DATA

5-1. Temperature Charts

Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
27