8-3-1. Checking the outdoor unit

8-3. Checking the Outdoor System

Work procedure
Apply 220 V AC between terminals L1 and L2 on the
outdoor unit terminal plate.
Short-circuit the T-RUN terminal to the COM terminal
of TEST/T-RUN terminals.
The LED (red) on the control board must illuminate.
The compressor and fan motor must turn ON.
(They turn ON about (70) seconds later after the power
is turned ON.)
No.
1
2
Check items (unit operation)
NOTE If the above check items are okay, but the outdoor unit does not operate, there may be a faulty
connection between the indoor unit and the outdoor unit.
73