9.2.Sensible Capacity Chart

OCS-E9GFEW-2 CU-E9GFE-2

 

220V

 

 

 

 

 

Outdoor Temp. (°C)

 

 

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30°C

 

 

35°C

 

 

40°C

 

 

46°C

 

 

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D.B.

 

W.B.

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17.0

2.48

2.13

0.52

2.32

2.05

0.56

2.16

1.97

0.60

1.96

1.88

0.65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

 

19.0

 

 

 

2.50

 

0.57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19.5

2.72

2.23

0.53

2.55

2.15

0.57

2.37

2.06

0.61

2.15

1.97

0.66

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22.0

2.96

2.31

0.54

2.77

2.22

0.58

2.58

2.13

0.62

2.34

2.03

0.67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCS-E12GFEW-2 CU-E12GFE-2

 

220V

 

 

 

 

 

Outdoor Temp. (°C)

 

 

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30°C

 

 

35°C

 

 

40°C

 

 

46°C

 

 

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D.B.

 

W.B.

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17.0

3.47

2.49

0.89

3.25

2.40

0.96

3.02

2.30

1.03

2.74

2.20

1.11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

 

19.0

 

 

 

3.50

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19.5

3.81

2.61

0.90

3.57

2.51

0.97

3.32

2.41

1.04

3.02

2.30

1.12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22.0

4.15

2.70

0.92

3.88

2.60

0.98

3.61

2.49

1.06

3.28

2.38

1.14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCS-E18GFEW-2 CU-E18GFE-2

 

220V

 

 

 

 

 

Outdoor Temp. (°C)

 

 

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30°C

 

 

35°C

 

 

40°C

 

 

46°C

 

 

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D.B.

 

W.B.

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17.0

4.96

3.26

1.44

4.64

3.14

1.54

4.32

3.01

1.65

3.92

2.87

1.78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

 

19.0

 

 

 

5.00

 

1.56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19.5

5.45

3.41

1.45

5.10

3.28

1.56

4.74

3.15

1.67

4.31

3.01

1.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22.0

5.92

3.53

1.47

5.55

3.40

1.58

5.16

3.26

1.70

4.69

3.11

1.83

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

- Total Cooling Capacity (kW)

Indoor 27°C/19°C

SHC

- Sensible Heat Capacity (kW)

Outdoor 35°C/24°C

IP

- Input Power (kW)

 

35