Pelco ALM2064 manual Table A. Switch, DIP Switch

Models: ALM2064

1 20
Download 20 pages 24.87 Kb
Page 13
Image 13
Table A. Switch 1

Table A. Switch 1

SW1 – Communications/Alarm Type Selection

 

Baud

 

 

 

Alarm Range

 

 

 

Alarm Mode

 

1-32

 

33-64

 

1200

Off

Off

Off

1-64

Off

Off

Off

Norm. Open

Off

 

Off

Off

 

Off

 

 

 

 

 

 

 

 

 

(Unsupervised)

 

 

2400

On

Off

Off

65-128

On

Off

Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4800

Off

On

Off

129-192

Off

On

Off

Norm. Closed

Off

 

On

Off

 

On

 

 

 

 

 

 

 

 

 

(Unsupervised)

 

 

9600

On

On

Off

193-256

On

On

Off

 

 

 

 

 

 

 

19200

Off

Off

On

257-320

Off

Off

On

Supervised

On

 

Off

On

 

Off

 

 

 

 

 

 

 

 

 

 

 

38400

On

Off

On

321-384

On

Off

On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57600

Off

On

On

385-448

Off

On

On

*Default to

On

 

On

On

 

On

115200

On

On

On

449

On

On

On

Norm. Open

 

 

 

 

 

 

 

 

 

 

DIP Switch

1

2

3

 

4

5

6

 

7

 

8

9

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*The alarm modes default to normally open when DIP switches 7-10 are set to an invalid condition (all On).

Table B. Switch 2

Address

 

 

 

 

SW2 – Address

 

 

 

 

1

Off

Off

Off

Off

 

Off

Off

 

Off

Off

Off

Off

2

On

Off

Off

Off

 

Off

Off

 

Off

Off

Off

Off

3

Off

On

Off

Off

 

Off

Off

 

Off

Off

Off

Off

4

On

On

Off

Off

 

Off

Off

 

Off

Off

Off

Off

5

Off

Off

On

Off

 

Off

Off

 

Off

Off

Off

Off

6

On

Off

On

Off

 

Off

Off

 

Off

Off

Off

Off

7

Off

On

On

Off

 

Off

Off

 

Off

Off

Off

Off

8

On

On

On

Off

 

Off

Off

 

Off

Off

Off

Off

9

Off

Off

Off

On

 

Off

Off

 

Off

Off

Off

Off

10

On

Off

Off

On

 

Off

Off

 

Off

Off

Off

Off

11

Off

On

Off

On

 

Off

Off

 

Off

Off

Off

Off

12

On

On

Off

On

 

Off

Off

 

Off

Off

Off

Off

13

Off

Off

On

On

 

Off

Off

 

Off

Off

Off

Off

14

On

Off

On

On

 

Off

Off

 

Off

Off

Off

Off

15

Off

On

On

On

 

Off

Off

 

Off

Off

Off

Off

16

On

On

On

On

 

Off

Off

 

Off

Off

Off

Off

DIP Switch

1

2

3

4

5

6

 

7

8

9

10

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

ON

ON

SERIAL PORT 1

BEGIN ALARM RANGE

BAUD RATE

1-64: OFF, OFF, OFF

1200: OFF, OFF, OFF

65-128: ON, OFF, OFF

2400: ON, OFF, OFF

129-192: OFF, ON, OFF

4800: OFF, ON , OFF

193-256: ON, ON, OFF

9600: ON, ON, OFF

257-320: OFF, OFF, ON

19200: OFF, OFF, ON

321-384: ON, OFF, ON

38400: ON, OFF, ON

385-448: OFF, ON, ON

57600: OFF, ON, ON

449: ON, ON, ON

115200: ON, ON, ON

 

N.O. = NORMALLY OPEN

N.C. = NORMALLY CLOSED

SUP = SUPERVISED

UNSUP = UNSUPERVISED

ALARM GROUP 33-64 N.O. UNSUP: OFF, OFF N.C. UNSUP: OFF, ON SUP: ON, OFF DEFAULT N.O.: ON, ON

ALARM GROUP 1-32 N.O. UNSUP: OFF, OFF N.C. UNSUP: OFF, ON SUP: ON, OFF DEFAULT N.O.: ON, ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT USED:

 

 

 

LOCAL DEVICE ADDRESS

OFF

 

 

 

 

 

DIAGNOSTICS: OFF

DEFAULT SETTINGS: LOCAL DEVICE ADDRESS 1, DIP SWITCH 9 OFF, DIP SWITCH 10 ON

NOTE: REFER TO APPENDIX A FOR SETTING EACH DEVICE ADDRESS (1-253)

DEFAULT SETTINGS: BAUD 19200, ALARM RANGE 1-64, ALARM GROUPS N.O.

00718

Figure 13. SW1 & SW2 Functions

C1517M-A (11/02)

13

Page 13
Image 13
Pelco ALM2064 manual Table A. Switch, DIP Switch