![WIRING ALARMS](/images/new-backgrounds/37201/3720113x1.webp)
WIRING ALARMS
All alarm wiring takes place using the four groups of connectors located on the rear of the alarm unit. The alarm unit has four groups of inputs. Each group represents 16 alarm inputs:
•Group I –
•Group II –
•Group III –
•Group IV –
Each of the four groups of wired alarm inputs are classified into modes (or contact types): supervised and unsupervised. This is important for the following reasons:
1.The operational mode (supervised or unsupervised) for each
2.Integrating supervised and unsupervised wiring modes within the same group is not allowed.
3.In unsupervised mode, it is not possible to have alarms wired for both normally open and normally closed operation in the same alarm group.
4.If wiring a group of alarm inputs as supervised, no unwired inputs are allowed as this would result in a constant alarm condition. All unwired inputs should have a
5.If wiring a group of alarm inputs as unsupervised and normally closed, no unwired inputs are allowed as this would also result in a constant alarm condition. Alarm inputs not used must be shorted out between the alarm input and its associated GND connection. Refer to Figure 7.
SW1 – SUPERVISED MODE
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
ON |
|
|
|
|
|
|
|
|
|
ALM GROUP ALM GROUP
7 | — ON | 9 — ON |
8 | — OFF | 10 — OFF |
SW1 – UNSUPERVISED MODE
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ALM GROUP |
|
|
|
|
| ALM GROUP | ||||||
|
|
| |||||||||||
|
|
|
|
|
|
| |||||||
| 7, | 8 | — OFF, OFF — N.O. | 9, 10 | — OFF, OFF — N.O | ||||||||
00710 | 7, | 8 | — OFF, ON — N.C. | 9, 10 | — OFF, ON — N.C |
Figure 5. DIP Switch Settings for Supervised/Unsupervised Modes
7 |