Table A. Video Coaxial Cable Requirements

Cable Type*

Maximum Distance

RG59/U

750 ft (229 m)

RG6/U

1,000 ft (305 m)

RG11/U

1,500 ft (457 m)

*Cable requirements:

75 ohms impedance All-copper center conductor

All-copper braided shield with 95% braid coverage

Table B. 24 VAC Wiring Distances

The following are the recommended maximum distances for 24 VAC applications and are calculated with a 10-percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for AC-powered devices.)

 

 

 

 

 

Wire Gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

18

16

14

12

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

consumedVATotal

10

283 (86)

451

(137)

716 (218)

1142

(348)

1811 (551)

2880 (877)

distanceMaximumfrom

totransformerload

 

 

 

 

 

 

 

 

 

20

141 (42)

225 (68)

358 (109)

571 (174)

905 (275)

1440 (438)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

94 (28)

150 (45)

238 (72)

380 (115)

603 (183)

960 (292)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

70 (21)

112 (34)

179 (54)

285

(86)

452 (137)

720 (219)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

56 (17)

90

(27)

143 (43)

228

(69)

362 (110)

576 (175)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXAMPLE: An enclosure that requires 30 VA and is installed 94 feet (28 m) from the transformer would require a minimum wire gauge of 20 AWG.

NOTE:

Models with heaters require 24 VAC for the heater. The heater uses 53 VA. If the camera uses 24 VAC, add the camera power to that of the heater and refer to Table B to determine the size of wire to use.

Distances are calculated in feet; values in parentheses are meters.

C2433M-D (9/06)

7