Pelco DD53TC16-X manual Repeat, System Condition, Alert Message

Models: DD53TC16-X

1 42
Download 42 pages 59.32 Kb
Page 32
Image 32
Alert

Alert

SPECTRA III

LANGUAGEENGLISH

<SYSTEM INFORMATION> <DISPLAY SETUP> <DOME SETTINGS>

ACK ALERT

RESET CAMERA

CYCLE CAMERA POWER

REBOOT SYSTEM

EXIT

NOTE: The Alert section only applies to Pressurized Spectra III dome systems with software version 1.25 or higher. Spectra III systems that are not pressurized or pressurized systems that do not have dome drive software version 1.25 or higher will not display this menu item. Software version 1.25 or higher includes the software to monitor temperature, pressure, and dew point for Pressurized Spectra III systems.

Sensors strategically placed inside the pressurized dome system continually monitor pressure, temperature, and dew point. If internal conditions reach unacceptable levels, an alert message appears on the screen describing the alert condition. Example: If pressure drops below 1 psig, “LOW PRESSURE” is displayed on the monitor.

The following system conditions will trigger an alert message:

DOME SETTINGS

<CAMERA>

<MOTION> <POWER UP> <LINE SYNC> <PRESETS> <PATTERNS> <ZONES>

<TITLE TEXT> <ALERT> <CLEAR> <PASSWORD>

BACK

EXIT

ALERT

 

 

 

REPEAT

CONSTANT

ACK ACTION

ALWAYS ON

ACTIVATE AUX

NO

<CURRENT READING>

 

RESET ALERT

 

BACK

 

EXIT

 

System Condition

Alert Message

Temperature is above 140°F (60°C)

HIGH TEMPERATURE

Temperature is below -40°F (-40°C)

LOW TEMPERATURE

Pressure is above 11 PSIG

HIGH PRESSURE

Pressure is below 1 PSIG

LOW PRESSURE

The difference between the temperature and the

DEW POINT (HIGH HUMIDITY)

dew point is less than or equal to 3°C.

 

 

 

The alert message will be repeatedly displayed until the system controller acknowledges the alert condition by selecting ACK ALERT in the main menu. Once acknowledged, the alert message changes to the programmed acknowledge action (ACK ACTION). If the alert condition remains active after a period of time, the alert message reappears on the monitor, restarting the alert message cycle. This cycle will continue to repeat until the alert condition is resolved.

REPEAT

This setting programs how often an alert message is repeatedly displayed until the system controller acknowledges the alert condition. The following are the settings for REPEAT:

CONSTANTThe alert message is continuously displayed on the monitor until acknowledged.

15 MIN

The alert message is displayed every 15 minutes for a 15-second

 

duration until acknowledged.

30 MIN

The alert message is displayed every 30 minutes for a 15-second

 

duration until acknowledged.

60 MIN

The alert message is displayed every 60 minutes for a 15-second

 

duration until acknowledged.