Appendix

Table A. Video Coaxial Cable Wiring Distances

Cable Type*

Maximum Distance

RG59/U

750 ft (229 m)

RG6/U

1,000 ft (305 m)

RG11/U

1,500 ft (457 m)

*Cable requirements: 75-ohm impedance

All-copper center conductor

All-copper braided shield with 95% braid coverage

Table B shows are the recommended maximum distances for 24 VAC applications and are calculated with a 10 percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for AC-powered devices.)

Table B. 24 VAC Wiring Distances

 

 

 

 

Wire Gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

18

16

14

12

10

 

 

 

 

 

 

 

 

 

 

 

10

283

451

716

1142

1811

2880

 

 

(86)

(137)

(218)

(348)

(551)

(877)

 

 

 

 

 

 

 

 

 

 

 

 

fromdistanceMaximum loadtotransformer

consumedVATotal

20

141

225

358

571

905

1440

(21)

(34)

(54)

(86)

(137)

(219)

 

 

(42)

(68)

(109)

(174)

(275)

(438)

 

 

 

 

 

 

 

 

 

 

 

30

94

150

238

380

603

960

 

 

(28)

(150)

(72)

(115)

(183)

(292)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

70

112

179

285

452

720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

56

90

143

228

362

576

 

 

(17)

(27)

(43)

(69)

(110)

(175)

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Distances are calculated in feet; values in parentheses are meters.

For example, an enclosure that requires 30 VA and is installed 94 ft (28 m) from the transformer would require a minimum wire gauge of 20 AWG.

Models with heaters require 24 VAC for the heater; the heater uses 58 VA. If the camera uses 24 VAC, add the camera power to that of the heater and refer to Table B to determine the size of wire to use.

C1458M-J (9/08)