Appendix
Table A. Video Coaxial Cable Wiring Distances
Cable Type*
Maximum Distance
RG59/U
750 ft (229 m)
RG6/U
1,000 ft (305 m)
RG11/U
1,500 ft (457 m)
*Cable requirements:
Table B shows are the recommended maximum distances for 24 VAC applications and are calculated with a 10 percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for
Table B. 24 VAC Wiring Distances
|
|
|
| Wire Gauge |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| 20 | 18 | 16 | 14 | 12 | 10 |
|
|
|
|
|
|
|
|
|
|
| 10 | 283 | 451 | 716 | 1142 | 1811 | 2880 |
|
| (86) | (137) | (218) | (348) | (551) | (877) |
| |
|
|
| ||||||
|
|
|
|
|
|
|
| fromdistanceMaximum loadtotransformer |
consumedVATotal | 20 | 141 | 225 | 358 | 571 | 905 | 1440 | |
(21) | (34) | (54) | (86) | (137) | (219) | |||
|
| (42) | (68) | (109) | (174) | (275) | (438) |
|
|
|
|
|
|
|
|
|
|
| 30 | 94 | 150 | 238 | 380 | 603 | 960 |
|
| (28) | (150) | (72) | (115) | (183) | (292) |
| |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| 40 | 70 | 112 | 179 | 285 | 452 | 720 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 50 | 56 | 90 | 143 | 228 | 362 | 576 |
|
| (17) | (27) | (43) | (69) | (110) | (175) |
| |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
NOTE: Distances are calculated in feet; values in parentheses are meters.
For example, an enclosure that requires 30 VA and is installed 94 ft (28 m) from the transformer would require a minimum wire gauge of 20 AWG.
Models with heaters require 24 VAC for the heater; the heater uses 58 VA. If the camera uses 24 VAC, add the camera power to that of the heater and refer to Table B to determine the size of wire to use.
13 |