Pentair 472645 Standard Features PowerMax PM, Model Nomenclature, Pennant Option Descriptions

Models: 472645

1 28
Download 28 pages 16.02 Kb
Page 6
Image 6
Standard Features PowerMax PM (500-2000)

Standard Features PowerMax PM (500-2000)

Automatic bypass

• Multiple operating gas valve/pressure

115/24VAC 75VA power from class 2

• ASME 160 psi working pressure heat

 

regulators

 

transformer

 

exchanger

• Manual “A” gas valve

Manual reset high limit

ASME “H” stamp

Intake air filter

Automatic reset high limit

Flanged water connections

• Multiple, removable burner trays

Electronic PID temperature control with

Glass-lined cast iron headers

Stainless steel burners

 

LCD and touchpad

External header gaskets

Built-in draft fan(s) for Category I or III

PC board for electrical connections

• 75 psi (817 kPa) ASME

 

venting

Hot surface ignition

 

rated pressure relief valve

Air pressure switch

On/Off toggle switch

Flow switch

Burner site glass

Pump time delay

Temperature and pressure gauge

24V control system

Diagnostic lights

 

 

 

 

• Convertible indoor or outdoor operation

 

 

 

 

Bronze trim

Model Nomenclature

1 2

P M

3

4

5

6

7

P

8 9

A

10

C

11

C

12 13

2

14 15

N

SERIES

PM = POWERMAX

APPLICATION

P- POOL

SIZE

MBTU/h

0 5 0 0

0 7 5 0

1 0 0 0

1 2 5 0

1 5 0 0

1 7 5 0

2 0 0 0

FUEL

 

ALTITUDE

 

LOCATION

 

N-NATURAL

 

0-10,000 ft

 

C- INDOOR

 

P-PROPANE

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

FIRING MODE

 

 

 

 

 

C- ON/OFF

 

 

 

 

 

 

 

 

REVISION

 

 

PUMP

 

 

2- SECOND

 

 

N-NORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT EXCHANGER

 

OPTIONS

B- GLASS LINED CAST IRON / COPPER /

 

X-STANDARD

 

BRONZE TRIM (Std)

 

J-CDS-1, IRI

K- BRONZE / COPPER

 

L-MN (indoor)

P- GLASS LINED CAST IRON / CuNi /

 

 

 

 

 

 

 

 

 

BRONZE TRIM

 

 

 

 

S- BRONZE / Cu-Ni

 

 

 

 

 

 

 

 

 

 

 

 

Pennant Option Descriptions

Code option J: for CSD-1, FM, IL (low water cutoff not included)

The changes made to the standard Pennant to achieve code option J are as follows:

Adds manual reset high and low gas pressure switches

Adds gas regulator

Changes ignition control from the standard three-attempt to a single attempt

Kit for IRI:

This kit is added to a Pennant unit with code option J. In total, code option J with the IRI kit:

Adds manual reset high and low gas pressure switches

Adds safety valve with gas regulator

Adds leak test valve for additonal safety

Adds normally open vent valve

Changes ignition control from the standard three-attempt to a single attempt

Code option L: for MN and LDS

 

 

Sizes 500 to 1000:

Sizes 1250 to 2000:

• Adds safety valve with regulator

• Adds solenoid safety valve

Adds high gas pressure switch

Adds motorized safety valve with proof of closure

Adds leak test valve

Adds leak test valve

Adds high and low gas pressure switches