FG-A1
Installation
1.Disconnect power to the primary sump pump.
2.Assemble control panel to battery box with four screws included.
3.Position 12 volt battery (not provided) into battery box.
4.Assemble the two lead wires from control panel to the battery with the two battery clamps included per Fig. 2.
Note: Assemble RED wire to POSITIVE (+) battery terminal and BLACK wire to the NEGATIVE
If this fuse must be replaced for any reason, it must be replaced with one of the exact same rating. Failure to do so may result in a fire hazard. If the polarities are connected wrong, the REVERSE battery indicator light on the control panel will come on. Correct the battery wire connections (replace the 1 amp fuse on control panels equipped with fuse).
If voltage of the battery is lower than DC 11 volts, the LOW battery indicator light will
come on and the buzzer sounds for the ALARM function. Battery should be checked by a battery shop.
5.Assemble
The enclosed pump includes a
Tee Fitting
30º |
| |
|
Figure 1 Tilting Pump
Bolt
Ring Terminal
Battery Post | Battery Clamp |
|
Figure 2 Attaching Ring Terminals and Battery Clamps
The other two ends of the tee will accept
The nylon belt with buckle, two rigid nylon straps and four screws are not needed and can be discarded.
6.Attach the float switch to the discharge pipe with a wire tie. Be sure that the turn off or down position of the float is above the suction inlet of this pump. Tether at
7.Insert the plug of the battery charger into the CHARGER socket of the control panel and plug the charger into an