Pentair FG-A1 Installation, Push the RESET button and the unit is ready for operation

Models: FG-A1

1 8
Download 8 pages 3.78 Kb
Page 4
Image 4
9.Push the RESET button and the unit is ready for operation.

FG-A1

Installation

8.Insert the plug of the pump into the PUMP socket of the control panel.

9.Push the RESET button and the unit is ready for operation.

10.The back-up sump pump should be checked by unplugging the primary sump pump and filling the sump basin with water. When the water level is slightly above the back-up sump pump it should turn on. As the water level drops, the back-up sump pump should turn off before the water level reaches the bottom of the back-up pump. If not, raise the float switch slightly. Press the RESET and plug the primary sump pump back in.

Note: Be sure that there is a 4" minimum from the top of the back-up pump to the top of the sump. The float switch should turn this pump ON near the top of the pump and at least 2" down from the top of the sump.

4 INCHES MINIMUM

1 INCH MINIMUM

PRIMARY SUMP PUMP (NOT INCLUDED)

RIGID 1-1/4" or 1-1/2" PVC or ABS DISCHARGE

PIPE (NOT INCLUDED)

FLOAT SWITCH

Manual backgroundManual background 1-1/4" TETHER

BACK-UP SUMP PUMP

(WITH BUILT-IN CHECK VALVE) (TILT PUMP 30°)

TEE ADAPTER

CHECK VALVE Manual background (NOT INCLUDED)

BATTERY BOX

SUMP BASIN

CONTROL PANEL

BATTERY CHARGER

4

Page 4
Image 4
Pentair service manual FG-A1 Installation, Push the RESET button and the unit is ready for operation