SETTING THE CLOCK

1.Push PROGRAM button until no flashing number appears on the right of the display. The clock is now in "time mode".

2.Push HOURS and MINUTES buttons until correct time of day is displayed NOTE: Pay attentinn to the AM/PM indicator.

PROGRAMMING

There are six possible programs during a 24 hour period for turning the pool equipment ON or OFF. More than one piece of equipment may be programmed ON or OFF at the same time.

1.Push PROGRAM button once A1 P ( lst Program) will flash on the right of the display. The clock is now in "program mode".

2.Enter desired program time by pushing the HOURS and MINUTES buttons In "program mode", minutes are advanced in ten minute increments Pay~ttentionto the AWPM indicator.

3.Push FILTER, CLNR, SPA, orAUX1 button to program equipment ON or OFF. The presence of a "flag" above each button indicates that the equipment is pre grammed ON. The absence of a "flag" indicates OFF.

4.Repeat the preceding sequence for the remaining five programs (2P6P). NOTE: Each time change requires a new program.

5.After programming, push PROGRAM button to return clock toL'timemode". If this is forgotten, after four minutes the clock will automatically return to "time mode".

3.If the spa is constructed in concrete and optional Spa-side Remote Control (model SS-100) is to be used, select a convenient location in the deck or above water level in

the spa wall SS-100 should not be submerged by the spa water.

Install a6" to 12" length of 1%" pvc pipe at this location to provide a receptable for S S

100. This pipe should be level and protrude beyond the finished surface of spa It can be cut back at a later date. Connect 1l/2" coupling and reducing bushing for

'either %" or %" conduit and provide conduit as necessary to location of LX-10 Service Center.

Do not install Outdoor Remote Control until spa construction is completed.

U - 10 SERVICE CENTER:

Select a convenient location (at the equipment pad area) to mount LX-10 Service Center. Ensure that the location is greater than 5 feet from the water'sedge and no further than 15 feet from the threeport valves Mount the LX-10 on a flat surface, using appropriate scr'ewsthrough the three external mounting points located on the side of the enclosure. Do not drill and mount from inside the enclosure. Install to provide drainage of compartment for electrical components

All low voltage connections are mads to printed circuit board, located behind hinged faceplate in left side compartment.

Strip jacket of Gpair cable 6" to identify the twisted pairs and assure correct c o p nections Strip insulation of each wire Y4", and connect to screw terminal inaccordance with wiring diagram located on inside of enclosure cover.

NOTE For the convenience of the serviceman, the screw terminal can be unplugged from printed circuit board without disconnecting wires

VALVE OPERATORS:

Mount Valve Operators (model VOR-24) to threeport valves in accordance with instructions printed on box

Plug cables into side of each Valve Operator, and run cables t~ low voltage compart- ment of LX-10 Service Center. Plug other end of cables into appropriate valve socket on printed circuit board: intake(suction) valve to INT valve socket, and return valve to RET .~alvesocket

WATER SENSOR:

Select a convenient location to mount Water Sensor(mode1 W S 5 L ) in the plumbing system at the filter pump Ensure that thislocation is nogreaterthan 10 feet from LX-10 Service Center, otherwise cable will need to be extended Disconnect Water Sensor from WTS- and WTSe terminals on printed circuit board of Time Master. Remove clamp kit from behind service panel in right side compartment of LX-10, and i ~ s t a lSensorl in accordance with instructions

Cautior.: Overtighting of clamp can cause deformation of O r i n g seal.

Run cable from Sensor I ~ a t i o ton low voltage compartment of LX-10. Cut off excess cable if necessary. Strip insulation l/4" and connect to black-green pair of 6pair cable in acco:dance with wiring diagram located inside LX-10 cover. Pay special attention to polarity of Sensor as indicated by color-coding.

GAS HEATER:

Inside the heater, interrupt wire between thermostat and gas valve, and connect2 c o p ductor cable with wire nut%in accordance with wiring diagram which is located inside LX-10 cover. Do not disconnect high limit and pressure switches

Run cable to LX-10 low voltagecompartment Strip insulation %", and connect to HTR terminals on printed circuit board

Page 4
Image 4
Pentair Time Master installation instructions Setting the Clock, Programming