CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

b. Copper pipes

Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.

3.Precautions during refrigerant piping work

Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and dust is even more important that in conventional piping).

a.Keep the open ends of all pipes sealed until connection with AC equipment is complete.

b.Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil, and lead to malfunctions in the equipment.

c.Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.

10.4. Installation, Transferring, Servicing

10.4.1.Inspecting Gas Leaks with a Vacuum Pump for New Installations (Using New Refrigerant Piping)

1.From the viewpoint of protecting the global environment, please do not release refrigerant into the atmosphere.

a.Connect the projecting side (pin-pushing side) of the charging hose for the manifold gauge to the service port of the 3-way valve. (1)

b.Fully open the handle Lo of the manifold gauge and run the vacuum pump. (2) (If the needle of the low-pressure gauge instantly reaches vacuum, re-check step a).)

c.Continue the vacuum process for at least 15 minutes, then check to make sure the low-pressure gauge has reached -0.1 MPa (-76 cmHg). Once the vacuum process has finished, fully close the handle Lo of the manifold gauge and stop the vacuum pump operation, then remove the charging hose that is connected to the vacuum pump adaptor. (Leave the unit in that condition for 1-2 minutes, and make sure that the needle of the manifold gauge does not return.) (2) and (3)

d.Turn the valve stem of the 2-way valve 90° counter-clockwise to open it, then, after 10 seconds, close it and inspect for a gas leak (4)

e.Remove the charging hose from the 3-way valve service port, then open both the 2-way valve and 3-way valve. (1) (4) (Turn the valve stem in the counter-clockwise direction until it gently makes contact. Do not turn it forcefully).

f.Tighten the service port cap with a torque wrench (18 N.m (1.8 kgf.m)). (5) Then tighten the 2-way valve and 3-way valve caps with a torque wrench (42 N.m (4.2 kgf.m)) or (55 N.m (5.5 kgf.m)). (6)

g.After attaching each of the caps, inspect for a gas leak around the cap area. (5) (6)

Precautions

Be sure to read the instructions for the vacuum pump, vacuum pump adaptor and manifold gauge prior to use, and follow the instructions carefully.

Make sure that the vacuum pump is filled with oil up to the designated line on the oil gauge.

The gas pressure back flow prevention valve on the charging hose is generally open during use. When you are removing the charging hose from the service port, it will come off more easily if you close this valve.

Fig. 12 Vacuum pump air purging configuration

49

Page 49
Image 49
Philips CS-E15DB4EW specifications Installation, Transferring, Servicing, Precautions

CS-E15DB4EW specifications

The Philips CS-E15DB4EW is an exceptional air conditioner that exemplifies modern cooling technology while emphasizing energy efficiency and user comfort. This model is designed to provide reliable performance in various settings, making it suitable for both residential and light commercial applications.

One of the standout features of the Philips CS-E15DB4EW is its powerful cooling capacity. With a cooling power reaching up to 15000 BTUs, this air conditioner is capable of effectively cooling medium to large-sized rooms. This high capacity ensures that users enjoy a refreshingly cool environment, even during the hottest summer months.

Energy efficiency is a prominent characteristic of the CS-E15DB4EW. It features an advanced inverter technology that optimizes power consumption while maintaining the desired temperature. This technology not only results in lower electricity bills but also reduces environmental impact by minimizing energy waste. The air conditioner boasts a high EER (Energy Efficiency Ratio), making it a responsible choice for energy-conscious consumers.

In terms of convenience, the CS-E15DB4EW is equipped with a user-friendly remote control, allowing users to adjust settings from a distance. This includes temperature adjustments, fan speed settings, and timer functions, providing flexibility and comfort at the users' fingertips. Additionally, the air conditioner features various operating modes, including cool, dry, and fan modes, catering to diverse climatic conditions and individual preferences.

Another remarkable characteristic of the Philips CS-E15DB4EW is its quiet operation. With a noise level as low as 30 dB, this unit ensures that users can enjoy a peaceful environment without the disruptive sounds typical of standard air conditioning units. This feature is particularly beneficial for bedrooms or study areas where concentration or relaxation is crucial.

Moreover, the unit is designed with a sleek, modern aesthetic that seamlessly integrates into any interior decor. The easy-to-clean filters and compact design contribute to its practicality, allowing for efficient maintenance and longevity.

In conclusion, the Philips CS-E15DB4EW stands out as a versatile, efficient, and user-friendly air conditioning solution. With its powerful cooling capacity, energy-saving technologies, convenient features, and quiet operation, it effectively addresses the cooling needs of various environments. Whether for residential use or light commercial applications, this model is designed to provide a comfortable atmosphere while being mindful of energy consumption and environmental impact.