10.Troubleshooting

__________________________________________________________

____

PROBLEM

POSSIBLE CAUSE

ACTION TO TAKE

UPS not on

On/off/test/silence

 

Press the on/off/test/silence

LED not light

button not pushed

or

button more than 1 second

 

push too short

 

 

 

Battery voltage less

than

Recharge the ups at least 4 hours

 

10V

 

 

 

PCB failure

 

Replace the PCB, call for service

 

Load less than 20W at

Normal condition

 

battery mode

 

 

UPS always at

Power cord lose

 

Replug the power cord

battery mode

AC FUSE burn out

 

Replace the AC fuse

 

Line voltage too high, too

Normal condition

 

low or black out

 

 

 

PCB failure

 

Replace PCB, call for service

Back up time

battery not fully charged

Recharge the UPS at least 4 hours

too short

PCB failure

 

Replace PCB, call for service

Buzzer

Overload

 

Remove the noncritical loads

continuous

 

 

 

beeping

 

 

 

 

 

 

 

RED LED light

Battery failure

 

Replace battery, call for service