LOW NOx TURBOPOWER® • PACKAGED WATER HEATER
NICKELSHIELD®
TANK SERIES 750 GALLONS VERTICAL
MODEL | Recovery gph c | INPUT | Min. Inlet | SCAQMD Energy | Dimensions |
| Blower | Shipping | ||||||
Flow Gas |
| (inches) |
| Motor | Weight | |||||||||
|
|
|
| |||||||||||
NUMBER | 40° - 120°F | 40° - 140°F | Btu/h | Pressure | Model No. | A |
| B | C | HP |
| Amps | # | |
|
| " W.C. d |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
1000 N | 1000 | 800 | 800,000 | 4.5 | 8TPL | 800 MBtu/h | 33 |
| 8 | 1 | 1/2 |
| 7 | 2740 |
1500 N | 1500 | 1200 | 1,200,000 | 4.5 | 12TPL | 1200 MBtu/h | 33 |
| 8 | 1 |
| 14 | 2780 |
cRecoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss. d With standard gas train
* The information presented is for natural gas 0.6 S.G. Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV 6452.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL. MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
VENTING REQUIREMENTS:
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."
STANDARD ELECTRICAL REQUIREMENTS:
VOLTAGE: 120V, 1Ø, 60 HZ., 20 AMPS.
OTHER VOLTAGES REQUIRE AN EXTERNAL
STEPDOWN TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND SPECIFICATION WITHOUT NOTICE.
Product is patented in the U.S., Canada, and Mexico.
| PVI INDUSTRIES, LLC |
PV 6530 02/25/04 | FORT WORTH, TEXAS 76111 |
(800) |