8.Do not install on carpet or other combustible floor coverings. If installation over a combustible floor is required, follow these guidelines:

Use a base of hollow clay tile or concrete blocks from 8" to 12" thick and extending 24" beyond the sides.

Place the blocks in line so that the holes line up horizontally to provide a clear passage through the blocks.

Install 1/2” fireproof millboard with a 20-gage sheet metal cover over the block base.

Center the unit on the base. Also follow this procedure if electrical conduit runs through the floor, and beneath the appliance. A field-installed base must meet all local fire and safety code requirements.

4.5Service Clearances

Allow sufficient space to provide adequate clearances on all sides for service and inspection. At least 24” above the water heater is required for filter replacement (if equipped) and burner/gas control service, 18” at left and right sides of the appliance. Optional equipment may increase the clearance requirements. Allow sufficient space for installing and servicing connections such as water, gas, vent, combustion air, electrical, pump and other auxiliary equipment.

4.6Clearances To Combustible Surfaces

Minimum 1” clearance must be provided from any vent surface to adjacent combustible material. The minimum clearances to unprotected combustible material are 24” be provided at the front, 8” be provided at the rear and 8” at top, left and right sides of the appliance.

5 GENERAL PIPING GUIDELINES

5.1Inlet and Outlet Connections

1.Use only non-ferrous water piping and fittings. Do not use galvanized pipe or fittings. Use of ferrous or galvanized pipe or fittings can cause rust to form.

2.Install shut-off valves and unions on the inlet and outlet water piping for servicing. Use caution when threading pipe nipples into tank connections to prevent cross threading, or over-tightening. Always use a back-up wrench on tank nipples when tightening unions, valves, etc.

3.Insulate hot water and return circulation lines. Insulate cold water supply lines if subject to freezing during shutdown periods. Important: Do not use the plumbing connected to the appliance as a ground for welding or any other purpose.

4.Pipe the drain valve to a suitable open drain.

5.2Building Return Piping

To maximize water heater efficiency, connect the building return (≈ 5 gpm) directly to the return fitting located at the rear of the tank.

11

PV500-44U 06/12

Page 11
Image 11
PVI Industries PV500-44U manual Service Clearances, Clearances To Combustible Surfaces, General Piping Guidelines

PV500-44U specifications

PVI Industries is a well-established name in the manufacturing of innovative water heating solutions, and one of its standout products is the PV500-44U. This commercial water heater is specifically designed to meet the demands of medium to large-scale facilities, ensuring efficient and reliable hot water delivery.

The PV500-44U is a high-capacity, gas-fired water heater, offering a remarkable output of up to 500,000 BTU per hour. This impressive capacity makes it suitable for a variety of applications, including hospitality, healthcare, and industrial washing. With such power, it provides continuous hot water, which is vital in settings that require consistent hot water availability.

One of the key features of the PV500-44U is its robust construction. The unit is designed with high-quality stainless steel, which provides durability and resistance against corrosion. This is crucial for maintaining long-term reliability, especially in environments where water quality may vary. Additionally, the water heater utilizes a sophisticated insulation system that minimizes heat loss, ensuring that energy consumption remains efficient.

The PV500-44U incorporates advanced technologies aimed at enhancing performance and user control. It features a state-of-the-art digital control system that allows for precise temperature settings and monitoring. This system not only ensures optimal performance but also enhances safety by providing alerts for any operational anomalies.

Another notable characteristic of the PV500-44U is its eco-friendly design. It is engineered to meet the latest environmental regulations, which helps reduce carbon emissions and energy consumption. The unit’s high thermal efficiency contributes to lower operating costs, making it an economical choice for businesses looking to manage their energy expenses effectively.

In terms of maintenance, the PV500-44U offers user-friendly access to components, simplifying routine servicing and repair tasks. This thoughtfully designed structure helps extend the lifespan of the unit and minimize downtime, which is critical for maintaining hot water availability in commercial settings.

Overall, the PVI Industries PV500-44U stands out as a reliable and efficient water heating solution that effectively meets the high demands of commercial applications. Its combination of powerful output, robust construction, advanced technology, and eco-friendly features makes it a premium choice for businesses seeking quality and efficiency in their hot water systems.