PVI Industries PV500-44U manual Single Unit Installation Suggested Pipe Size, Nominal Iron, Inches

Models: PV500-44U

1 42
Download 42 pages 44.94 Kb
Page 16
Image 16
SINGLE UNIT INSTALLATION SUGGESTED PIPE SIZE

Use this corrected total distance from the meter for determining the suggested pipe size in the “Single Unit Installation Suggested Gas Pipe Size” table.

 

 

 

SINGLE UNIT INSTALLATION SUGGESTED PIPE SIZE

 

Equivalent Feet

 

 

Maximum Capacity for Natural Gas*

 

 

 

MBTU/HR Based on 0.5" W.C. Pressure Drop**

 

From Meter

 

 

 

 

1-1/4"

1-1/2"

2"

2½"

3"

4"

 

 

25

 

860

1320

2475

3900

7000

-

40

 

660

990

1900

3000

5300

-

60

 

-

810

1520

2400

4300

-

80

 

-

690

1300

2050

3700

-

100

 

-

620

1150

1850

3250

6700

125

 

-

-

1020

1650

2950

6000

150

 

-

-

950

1500

2650

5500

175

 

-

-

850

1370

2450

5000

200

 

-

-

800

1280

2280

4600

*Multiplier for Propane: 1.57

**Multiplier for alternate pressure drops: 0.3" W.C. 0.77; 1.0" W.C. 1.41; 2.0" W.C. 2.00; and 4.0" W.C. 2.82.

MULTIPLE UNIT INSTALLATIONS GAS PIPING SIZE CHART

Maximum Capacity of Pipe in Thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025BTU’s per Cubic

Foot of Gas and 0.60 Specific Gravity).

Nominal Iron

 

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

Pipe Size,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inches

10

20

30

40

50

60

70

80

90

100

125

150

175

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

697

477

384

328

292

267

246

256

210

200

179

164

49

138

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4100

2820

2260

1950

1720

1560

1440

1330

1250

1180

1100

974

871

820

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1/2

6460

4460

3610

3100

2720

2460

2310

2100

2000

1900

1700

1540

1400

1300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

11200

7900

6400

5400

4870

4410

4000

3800

3540

3300

3000

2720

2500

2340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

23500

16100

13100

11100

10000

9000

8300

7690

7380

6870

6150

5640

5130

4720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.6Appliance Isolation during Gas Supply Piping Pressure Test

1.The appliance and its provided manual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ PSI (3.5 kPa).

2.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ PSI (3.5 kPa).

3.The appliance and its gas connection must be leak-tested before placing it in operation.