QHT B3-B9 installation instructions Piping the Boiler, Safety Relief Valve

Models: B3-B9

1 36
Download 36 pages 5.67 Kb
Page 12
Image 12

5. Piping the Boiler

All piping must conform to state and local codes. Page 11 shows the location and size of the boiler tappings. It is recommended to install unions and gate valves at the inlet and outlet of the boiler, so it may be readily isolated for service.

For Canadian installations, a low water cut off is required if the boiler is installed above the level of radiation. Even if the boiler is installed below the level of radiation it is strongly recommended that a low water cut off be installed. Install manual and/or automatic air venting devices at the high points in the system to eliminate trapped air. The weight of all piping should be supported by suitable hangars and floor stands, not by the boiler’s purging/expansion station. Clearance for hot water pipes are 1 inch to combustibles. The make-up water line must be piped into the boiler and be fitted with a backflow preventer and a pressure- reducing valve to reduce line pressure to 10 to 15 psi.

In the case of a gas installation, the boiler should be installed such that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacement, etc.).

If the boiler is to be used in conjunction with a chilled water system, it must be piped with the appropriate valves to ensure the chilled medium does not enter the boiler. If the boiler is connected to heating coils in an air handling system, where the coils could be exposed to cold air circulation, provisions for freeze protection control must be installed. The boiler must have flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.

NOTE: If the heating system is to be filled with antifreeze, use only formulations expressly made for hydronic heating systems (such as propylene glycol). Do not use automotive types of antifreeze (ethylene glycol). Use of antifreeze will alter system output and characteristics. Consult a factory representative for details or assistance.

SAFETY RELIEF VALVE

1.The safety relief valve should be piped into one of the two upper tapings in the rear of the boiler

2.The relief valve should be installed using the hardware supplied in the trim kit without valving between the PRV and the boiler.

3.Pipe the discharge for the safety relief valve with copper tube to within four inches from the floor to prevent injury in the event or a pressure release. Provide piping that is the same size as the safety relief valve outlet.

Page 12

Page 12
Image 12
QHT B3-B9 installation instructions Piping the Boiler, Safety Relief Valve