1. The pool heater(s) shall be fired with |
| gas at a rated input of |
| BTU/hr. |
2.The pool heater(s) shall be CSA tested and certified with a minimum thermal efficiency of 85 percent at full fire.
3.The pool heater(s) shall be ASME inspected and
4.The pool heater(s) shall have a floor loading of 65 lbs. /square foot or less.
B.Heat Exchanger
1.The heat exchanger shall be of a
2.The heat exchanger shall be sealed to 160 PSIG rated bronze headers with silicone "O" rings, having a temperature rating over 500°F.
3.The low water volume heat exchanger shall be
4.The headers shall be secured to the tube sheet by stud bolts with flange nuts to permit inspection and maintenance without removal of external piping connections. The heat exchanger shall incorporate "V” baffles between the tubes to ensure complete contact of the external tube surfaces with the products of combustion.
5.The pool heater(s) shall be capable of operating at inlet water temperatures as low as 105°F without condensation.
6.The pool heater(s) shall be designed to accommodate field changes of either left or right hand plumbing and electrical while leaving the tube bundle in place.
C.Burners
1.The tubular burners shall have multiport radial gas orifices, punched ports and slots, be capable of quiet ignition and extinction without flashback at the orifice, and be manufactured from
2.The burners will be supplied with a
D.Pilot Control System
1.The pool heater(s) shall be equipped with a 100 percent safety shutdown system.
2.The ignition shall be Hot Surface Ignition type with full flame rectification by remote sensing separate from the ignition source, with a
3.The igniter will be located away from the water inlet to protect the device from condensation during startup.
4.The ignition control module shall include an LED that indicates six (6) individual diagnostic flash codes.
5.Two external viewing ports shall be provided, permitting visual observation of burner operation.
E.Gas Train
1.The pool heater(s) shall have a firing/leak test valve and pressure test valve as required by
2.The pool heater(s) shall have
3.Gas control trains shall have a redundant safety
F.Pool Heater Control
1.The following safety controls shall be provided:
a.High limit control
b.Flow switch, mounted and wired
c.125 PSIG ASME pressure relief valve, piped by the installer to an approved drain
d.Temperature and pressure gauge
e.Poolstat
2.The pool heater(s) shall be equipped with an
Project Name / Date | 2 |