Raytherm - Type WH

Models 2100-4100

Model

MODELS WH 2100 – 4001

Model

MBTUH

Width

Overall

Gas

Water

Flue

Approx.

Height

Conn.

Conn.

Dia.

Shipping

No.

 

 

 

Input

Output

A

B

G

H

K

Weight (lbs)

 

WH-2100

2100

1722

61

68-1/4

*

3

24

1400

WH-2500

2499

2049

70

68-1/4

*

3

26

1580

WH-3001

3000

2460

81-1/4

68-1/4

2

3

28

1750

WH-3500

3500

2870

92-1/2

68-1/4

2

3

30

1920

WH-4001

4000

3280

103-3/4

68-1/4

2

3

32

2100

* 1-1/2” or 2”, contingent on water heater type code requirements

NOTES: Dimensions are in inches.

Ratings are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for every 1,000 feet above sea level.

HEATER RATES OF FLOW AND PRESSURE DROPS

Model

20°F ∆T

30°F ∆T

40°F ∆T

No.

GPM

∆P (ft)

GPM

∆P (ft)

GPM

∆P (ft)

WH-2100

172

11.0

115

4.9

N/A

N/A

WH-2500

N/A

N/A

137

7.5

102

4.3

WH-3001

N/A

N/A

164

11.2

123

6.5

WH-3500

N/A

N/A

191

16.8

144

9.3

WH-4001

N/A

N/A

N/A

N/A

164

12.8

HEATER RECOVERY RATES (GPH)

Model

 

 

Temperature Rise

 

 

No.

20°F

30°F

40°F

50°F

60°F

80°F

100°F

WH-2100

10336

6890

5168

4134

3445

2584

2067

WH-2500

12300

8200

6150

4920

4100

3075

2460

WH-3001

14765

9844

7383

5906

4922

3691

2953

WH-3500

17227

11484

8613

6891

5742

4301

3445

WH-4001

19688

13125

9844

7875

6563

4922

3938

Maximum acceptable flow through heat exchanger tubes is 200 GPM.

Raypak, Inc. ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com

Catalog No.: 3500.24B

Effective: 1-15-08

Replaces: 7-15-04

Page 2
Image 2
Raypak 2100 - 4001 warranty Raytherm Type WH, Models WH 2100