Raypak H-0066B Burner Inspection, Venting System Inspection, Circulator Water Pump Inspection

Models: H-0135B H-0066B H-0180B H-0090B H-0030B H-0042B

1 4
Download 4 pages 24.44 Kb
Page 4
Image 4
1. Burner Inspection.

1. Burner Inspection.

Clean the main burners and air louvers of dust, lint and debris. With burner in operation, make a visual check of the burner flame and the pilot flame (when equipped). Yellow flames indicate some restriction of combustion air openings. A bright orange, luminous flame is not normal and can cause sooting under prolonged operation. Should this condition be ob- served, contact immediately a qualified service agency to correct the problem.

2. Venting System Inspection.

Visually inspect the venting system. Make sure the vent connections are secure and have not become disengaged. Look for any indication of corrosion, or carbon (soot) streaks which could cause leakage of products of combustion into the living space. Inspect the vent terminal outside the building. Make sure it is not damaged to cause blockage or restriction of the flue gas. Observe for any indication of soot. The presence of soot accumulation in the vent terminal would indicate an abnormal operating condition. This should be investigated and corrected by a qualified service agency.

SOOT

CORROSION

DISENGAGED

3. Circulator (Water Pump) Inspection.

The circulator is permanently lubricated and thus, will not require any lubrication. Inspect for evidence of water leakage. This should be corrected to prevent any possible damage to electrical components of the boiler.

CAUTION: In case of a prolonged power failure during freezing weather conditions, boiler and piping system must be drained completely to avoid possible damage to the heating system.

To prevent the potential freezing damage to the heating system, it is recommended that the following system shut down procedure be performed.

SYSTEM SHUT DOWN PROCEDURE

1. Set the room thermostat to "OFF" or the lowest setting.

2. Turn off all electric switches to the boiler.

3. Turn off all gas valves supplying gas to the boiler. Refer to operating instruction label on the boiler.

4. Shut off the water supply to the boiler piping system loop.

5. Open drain valve on the boiler to remove water from the boiler and the piping circuits.

NOTE: It may be necessary to open the purge valves and/or manual air vents to facilitate complete drainage of water from the heating system.

4. Service Assistance.

If service is required on the boiler, contact your local service agency or Raypak, Inc. can refer you to the proper qualified service agency. It is important and very often will save time if you state the model number, serial number and type of gas used. This information will be found on the nameplate of the boiler.

Fig.#8204.0

Raypak, Inc., 31111 Agoura Road, Westlake Village, CA 91361-4699 (818) 889-1500 FAX (818) 889-4522

Litho in U.S.A.

www.raypak.com

4

Page 4
Image 4
Raypak H-0066B, H-0042B Burner Inspection, Venting System Inspection, Circulator Water Pump Inspection, Service Assistance