Raypak P-4001, P-1826, P-926 Venting of Diaphragm Gas Components, Model, 1-1/4”, 1-1/2”, 2-1/2”

Models: P-2100 P-926 P-4001 P-1826

1 36
Download 36 pages 20.2 Kb
Page 9
Image 9
Venting of Diaphragm Gas

MANUAL

MANOMETER

SHUTOFF

 

VALVE

 

GAS PRESSURE

TEST UPSTREAM

GAS PRESSURE

TEST AT GAS

VALVE

GAS PRESSURE TEST

AT HEATER

Fig. 6: Gas Pressure Test Points

Venting of Diaphragm Gas

Components

Heaters with gas train components that have diaphragms in their construction are supplied with a bleed line connection that must be connected to the outside atmosphere as required by the National Fuel

Gas Code. Under NO circumstances shall bleed lines terminate in the gas utilization equipment flue or exhaust system.

Bleed Line

Connection

Fig. 7: Bleed Line Connection

Model

N

1”

P

1-1/4”

1-1/2”

N

2”

P

2-1/2”

N

3”

P

N

4”

P

No.

 

N

P

N

P

 

N

P

 

 

926/962

 

 

15

20

45

45

110

150

 

360

400

 

 

 

 

 

 

 

1083/1125

 

 

10

15

35

35

80

120

 

300

300

 

 

 

 

 

 

 

1178/1223

 

 

 

 

25

25

60

85

 

220

200

325

560

 

 

 

 

1287/1336

 

 

 

 

25

20

55

75

 

180

170

 

 

 

 

1414/1468

 

 

 

 

20

15

45

65

 

150

165

300

500

 

 

 

 

1571/1631

 

 

 

 

15

15

35

50

 

20

125

250

400

 

 

 

 

1758/1826

 

 

 

 

15

10

30

40

 

100

100

225

340

 

 

 

 

2100

 

 

 

 

10

10

25

30

 

80

75

175

260

400

600

 

2500

 

 

 

 

 

 

15

20

 

55

55

135

160

 

3001

 

 

 

 

 

 

10

15

 

35

40

85

120

250

500

600

3500

 

 

 

 

 

 

 

10

 

30

30

45

80

 

200

400

4001

 

 

 

 

 

 

 

5

 

20

25

35

65

 

160

300

400

Natural Gas, 1000 BTU/FT3 .60 Specific Gravity @ 0.5 in. WC Pressure Drop

Propane Gas, 2500 BTU/FT3 1.53 Specific Gravity @ 0.6 in. WC Pressure Drop

Table B: Maximum Equivalent Pipe Length