MANUAL | MANOMETER |
SHUTOFF |
|
VALVE |
|
GAS PRESSURE
TEST UPSTREAM
GAS PRESSURE
TEST AT GAS
VALVE
GAS PRESSURE TEST
AT HEATER
Fig. 6: Gas Pressure Test Points
Venting of Diaphragm Gas
Components
Heaters with gas train components that have diaphragms in their construction are supplied with a bleed line connection that must be connected to the outside atmosphere as required by the National Fuel
Gas Code. Under NO circumstances shall bleed lines terminate in the gas utilization equipment flue or exhaust system.
Bleed Line
Connection
Fig. 7: Bleed Line Connection
Model | N | 1” | P |
|
| N | 2” | P |
| N | 3” | P | N | 4” | P | |||
No. |
| N | P | N | P |
| N | P |
|
| ||||||||
926/962 |
|
| 15 | 20 | 45 | 45 | 110 | 150 |
| 360 | 400 |
|
|
|
|
|
|
|
1083/1125 |
|
| 10 | 15 | 35 | 35 | 80 | 120 |
| 300 | 300 |
|
|
|
|
|
|
|
1178/1223 |
|
|
|
| 25 | 25 | 60 | 85 |
| 220 | 200 | 325 | 560 |
|
|
|
| |
1287/1336 |
|
|
|
| 25 | 20 | 55 | 75 |
| 180 | 170 |
|
|
|
| |||
1414/1468 |
|
|
|
| 20 | 15 | 45 | 65 |
| 150 | 165 | 300 | 500 |
|
|
|
| |
1571/1631 |
|
|
|
| 15 | 15 | 35 | 50 |
| 20 | 125 | 250 | 400 |
|
|
|
| |
1758/1826 |
|
|
|
| 15 | 10 | 30 | 40 |
| 100 | 100 | 225 | 340 |
|
|
|
| |
2100 |
|
|
|
| 10 | 10 | 25 | 30 |
| 80 | 75 | 175 | 260 | 400 | 600 |
| ||
2500 |
|
|
|
|
|
| 15 | 20 |
| 55 | 55 | 135 | 160 |
| ||||
3001 |
|
|
|
|
|
| 10 | 15 |
| 35 | 40 | 85 | 120 | 250 | 500 | 600 | ||
3500 |
|
|
|
|
|
|
| 10 |
| 30 | 30 | 45 | 80 |
| 200 | 400 | ||
4001 |
|
|
|
|
|
|
| 5 |
| 20 | 25 | 35 | 65 |
| 160 | 300 | 400 |
Natural Gas, 1000 BTU/FT3 .60 Specific Gravity @ 0.5 in. WC Pressure Drop
Propane Gas, 2500 BTU/FT3 1.53 Specific Gravity @ 0.6 in. WC Pressure Drop
Table B: Maximum Equivalent Pipe Length
9