Regency R90 Clearances Requirements, Wood Fireplaces, Combustibles may not extend to unit face

Models: R90

1 3
Download 3 pages 21.14 Kb
Page 2
Image 2
Clearances Requirements

Wood Fireplaces

Wood Fireplaces

R90 Wood Fireplace

Clearances Requirements

No combustible materials on the face of unit.

Required Hearth must be non-combustible and will require thermal protection. Minimum thermal protection must have a "k" factor of 20.07 (in Canada), 0.84 (in US).

D

C

A

 

 

F

J

 

B

 

 

B

 

 

 

 

H

I

G

K

 

E

 

 

Clearance:

Dimension

Measured From:
USA Only

Canada Only

 

 

A: Mantel

18” (457mm)

18” (457mm)

Minimum (See Page 86)

Height

 

 

 

B: Sidewall

18” (457mm)

24” (610mm)

Side of fi replace

opening

 

 

 

C: Ceiling

46” (1168mm)

46” (1168mm)

Top of fi replace

opening

 

 

 

D: Mantel

10” (254mm)

10” (254mm)

Maximum (See Page 86)

Depth

 

 

 

E: Alcove

N/A

N/A

Approved for Single

Width

Sidewall only

 

 

 

 

 

 

F: Alcove

N/A

N/A

Approved for Single

Depth

Sidewall only

 

 

G: Thermal

 

 

Bottom to top of

Protection

1/2” (13mm)

1/2” (13mm)

Protection.

Height

 

 

 

 

 

H: Hearth

40” (1016mm)

40” (1016mm)

Edge to Edge of Hearth

Width

 

 

 

I: Hearth

18 ” (457mm)

18 ” (457mm)

Front of Hearth to Wall

Depth

 

 

 

J: Facing

52-1/2”

51-1/2”

Floor to Facing

Height**

(1334mm)

(1308mm)

Height**

K: Facing

44” (1118mm)

60” (1524mm)

Edge to Edge of

Width**

Facing**

 

 

**Required non-combustible facing.

172

Combustibles may not extend to unit face.

Do not notch wallboard around standoffs.

The R90 may be placed on or near construction materials. The combustion air kit, fi re stop spacer and roof fl ashings (not chase

ashings) may be placed directly on or against normal construction materials. The chimney requires a minimum 2" (51mm) clearance. A combustible mantle (to a depth of 10", 254mm) may be installed no closer than 18" (457mm) above the warm air vent or 55-1/2" (1410mm) from bottom of unit.

The chimney must be enclosed when installed in or passing through a living area where combustible material or people may come in contact with it. This is important to prevent possible personal injury or fi re hazard.

For any further information, please call your dealer. Special restrictions apply to the front and facing of the fi replace and nearby walls.

WARNING: If insulation is used, do not place the unit against it. Insulation or vapor barriers, if used, must be secured to assure insulation and vapor barriers remain in place and do not affect the required air spaces.

WARNING: Do not pack or fi ll required air spaces with insulation or other material. No material of any kind is allowed in these areas.

NOTES:

1)Do not insulate the chase cavity with blown or fi ll type insulation materials.

2)Local codes may not require a firestop at the ceiling level for outside chase installations; however, it is recommended for safety and the reduction of heat loss.

3)We recommend that you insulate at least the first floor of the chase to prevent heat loss.

4)Some local codes require 1 hour fi re rating on one or all sides of fi re chases. Check with your local authorities.

NOTES:

1)Minimum Chase sizes must be met according to the framing directions (page 149). US Installations will require a minimum ventilation with one 30 sq. in. (194 sq. cm.) opening grill (air is drawn from within the home not outside).

2)Mantel min. Height of 18” (457mm) from top of louver opening to underneath mantel or 55 1/2” (1410mm) from bottom of unit.

3)Minimum non-combustible facing must be installed according to the table on this page. Finishing material to be installed on top of this.

4)Framing is slightly larger than unit dimensions to allow for easier installation (50 3/4”, 1289mm h x 44”, 1118mm w)

5)Must maintain a min. of 46” (1168mm) from top of louver opening to fi nished ceiling.

6)Sidewall clearances, as detailed on this page, must be maintained according to your location.

7)Hearth must be a min. 40” (1016mm) wide x 18” (457mm) deep and 1/2” (127mm) thick.

June 2007 Regency Product Specifications Book
Page 2
Image 2
Regency Clearances Requirements, Wood Fireplaces, No combustible materials on the face of unit, R90 Wood Fireplace